Disinfection Configuration (Engineering Level Only)
(09,
Enter minimum temperature required to disinfect.
If checked, the flow rate will be reduced during disinfections to save water.
Enter minimum disinfection duration.
If disinfection temperature is not reached within this period, then disinfection
will be cancelled (if unsure, leave as default).
If disinfection is not completed within this period, then disinfection will be
cancelled (if unsure, leave as default).
Disinfection Configuration
Min. Temp. (°F)
Type
Standard
Read
Write
Min. Time (mins)
Max. Warmup (mins)
Max. Duration (mins)
Flow
(09,
Disinfection Configuration
Min. Temp. (°F)
Type
Energy Saving
Read
Write
Min. Time (mins)
Max. Warmup (mins)
Max. Duration (mins)
Flow
Upper Temp. (°F)
Reduced
Reduced
If “
Type
(Energy Saving)
” is selected, then the valve will reduce the required
period for disinfection proportionally as the temperature increases up to the
limit specified in “
Upper Temp. (°F)
”.
Warning!
Time reduction is not permitted by some National/Local
Regulations. If in doubt, select “
Standard
” settings.
(09,
Service Data (Engineering Level Only)
Service Data
Valve is OK
Last Serviced By 1234
on 7/21/2005 at 3:07 PM
“
Valve is OK
” means that no errors have been detected by the valve.
User ID and Date of last service.
Tap here to set the Serviced Date in the valve to the current date.
Set Service Date