background image

17

(09,

Valve

Service Flush

Temp. (F)

Duration (mins)

Read

Write

Disinfection

Service Flush

Options

Days

Hours

Wait Time

Setting Disinfection: Step 1, Valve Setup

Check 

…

 this box to enable

disinfection.

Note!

 Changes will not be stored in valve until “

Write

” is tapped (refer to “

Storing Setup to Valve

”).

Check 

…

 this box to select this

outlet   for disinfection.

Note!

 Changes will not be stored in valve until “

Write

” is tapped (refer to “

Storing Setup to Valve

”).

Setting Disinfection: Step 2, Outlet Setup

9

9

(09,

Outlet

Temperatures (°F)

Max.

Default

Min.

Full Cold

Disinfection

Service Flush

Read

Write

Options

‘Disinfection’ in Valve
Setup must be checked to
enable this function

Check that “

Disinfection

” is checked.

Содержание Brain Wave

Страница 1: ...Programmer Software Guide BrainWave is a registered trademark of Armstrong Hot Water Inc a division of Armstrong International Inc BrainWave features Rada technology Rada is registered to Kohler Mira...

Страница 2: ...al Disinfection Saving Log 12 Thermal Disinfection Failed Disinfection 13 ENGINEERING LEVEL 14 Login and Read Valve Data 14 Main Menu 15 Setting Service Flush Step 1 Valve Setup 16 Setting Service Flu...

Страница 3: ...computer follow the instructions below Insert the CD ROM The CD should start automatically If the CD does not start automatically then please use the support instructions on the CD wallet Select the i...

Страница 4: ...number List of valid users and IDs Tap Enter ID Name Enter Password Password Admin PASSWORD ADMINISTRATION Setting up Users and Passwords for a New Installation A new software installation will have n...

Страница 5: ...Click here to make the keyboard appear ID Read Valve Data Reading Valve Aim the Programmer at the Control Panel Read Valve Data 2 Ensure Control Panel is disabled Aim PDA at Control Panel and tap Rea...

Страница 6: ...09 Outlet Setup Flow Times Disinfection Rada Sense Main Menu 09 Valve Disinfection Arm Trigger Read Log Clear Log 09 Outlet Flow Times Mins Secs Read Write 09 Outlet Temperatures F Max Min Full Cold...

Страница 7: ...ad Log Clear Log Rada Sense Main Menu Main Menu Bath Shower 09 Outlet Temperatures F Max Default Min Options Full Cold Disinfection Service Flush Read Write Options Full Cold Disinfection Service Flus...

Страница 8: ...low Times 09 Shower Bath Flow Times Mins Secs Read Write Note Changes will not be stored in valve until Write is tapped refer to Storing Setup to the Valve 9 Enter the flow time before automatic switc...

Страница 9: ...ored If OK is NOT displayed or an error is displayed then the changes have not been stored Caution The outlet temperature must be re checked after a new temperature has been programmed refer to Checki...

Страница 10: ...he disinfection programme is factory set for a minimum of 5 minutes at 140 F If you need to change the configuration refer to ENGINEERING LEVEL WARNING The water flow during disinfection will be very...

Страница 11: ...ountdown reaches 0 Note The Control Panel is enabled during disinfection if any sensor is activated then the disinfection cycle is aborted WARNING For continued protection against legionella thermal d...

Страница 12: ...sinfection Checking for Completion Reading the disinfection log Disinfection Completed indicates temperature held for correct time 09 Valve Disinfection Arm Trigger Read Log Clear Log Disinfection Log...

Страница 13: ...Disinfection Failed Disinfection 09 Disinfection failed Indicates temperature not held for long enough Check water supply and disinfect once it has been corrected Disinfection Log Disinfection failed...

Страница 14: ...sure Control Panel is disabled Aim PDA at Control Panel and tap Read Valve Data button Ensure Control Panel is disabled Aim PDA at Control Panel and tap Read Valve Data button ENGINEERING LEVEL Login...

Страница 15: ...Data Service Data Valve Calibration 09 Valve Service Flush Temp F Duration mins Read Write Disinfection Service Flush Flow Times Disinfection Main Menu Outlet Setup Valve Setup Engineering Options Re...

Страница 16: ...eck this box to enable Service flush Note Changes will not be stored in valve until Write is tapped refer to Storing Setup to Valve Enter temperature duration and wait time Setting Service Flush Step...

Страница 17: ...rite is tapped refer to Storing Setup to Valve Check this box to select this outlet for disinfection Note Changes will not be stored in valve until Write is tapped refer to Storing Setup to Valve Sett...

Страница 18: ...Commissioned on 7 4 2005 at 6 53 PM EMV 1 Set Commission Data 09 Tap on one of these Options Service Data Valve is OK Last serviced by 1234 on 7 21 2005 at 3 07 PM Set Service Date Valve Calibration D...

Страница 19: ...oftware is in the control panel Note Not shown on older versions of Interface Software 09 Commissioning Data Engineering Level Only Location text can be set here Tap here to display the keyboard Tap h...

Страница 20: ...ation mins Flow 09 Disinfection Configuration Min Temp F Type Energy Saving Read Write Min Time mins Max Warmup mins Max Duration mins Flow Upper Temp F Reduced Reduced If Type Energy Saving is select...

Страница 21: ...fection Since last used Stepper Motor Pulses Days These are counted from when the valve is first switched ON Either time since the valve was last used or since the last Service flush This indicates ho...

Страница 22: ...ailure reinstate supply c Safety circuit may require resetting enable the control panel with magnetic key to reset d If the symptom has not been rectified contact Armstrong Hot Water Inc A fault has o...

Страница 23: ...RROR MESSAGES Control Panel not disabled or Programmer not aimed at Programming window Lost connection during communication Failed to connect Please try again Or Control panel not Ready Lost Connectio...

Страница 24: ...Armstrong s repair or replacement of the part or product excluding any labor or any other cost to remove or install said part or product or at Armstrong s option to repayment of the purchase price As...