10
Thermal Disinfection (Arming)
If “
Disinfection not enabled
” is displayed, refer to “
ENGINEERING LEVEL
”,
section “
Setting Disinfection: Step 1, Valve Setup
”.
Disinfection is Armed when the box turns green.
(09,
(09,
Valve Disinfection
Arm
Trigger
Read Log
Clear Log
Arming
Valve Disinfection
Thermal Disinfection
Disable User Interface
Arm
Trigger
Read Log
Clear Log
Note!
The disinfection programme is factory set for a minimum of 5 minutes at 140°F.
If you need to change the configuration, refer to ‘
ENGINEERING LEVEL
’.
WARNING!
The water flow during disinfection will be very hot and may scald on
contact. The valve must be supervised throughout the disinfection process and no-one
should approach the outlet within 3 metres.
Disable the Control Panel with
the magnetic key.
Aim the Programmer at the Control Panel
and tap “
Arm
”.
Disinfection not enabled
Check that “
Disinfection
” is checked.
Refer to “
Setting Disinfection: Step 2, Outlet Setup
”.