Diagnostic: Power Is Low
Functional Behavior:
The following diagnostic flags are set: “Maintenance Required Status” and “Power Is Low: Maintenance is
needed mid-term” (Bit 28 and Bit 19 are set to 1).
Causes and Triggers:
The diagnostic flag is set if the remaining battery capacity (DLMO.PowerSupplyStatus = 3 ) is less than
25% and battery life (DLMO.EnergyLeft) is more than 10 days.
Diagnostic: Communication Error (Armstrong specific)
Functional Behavior:
Diagnostic: Communication error (Armstrong specific) (Bit 28 and Bit 3 are set to 1).
Causes and Triggers:
The diagnostic flag is set if the API communication between application processor and stack radio module
is not working. If no Radio API Request/Response will be received by the application processor during last
5 minutes the flag is set. If an API Request/Response is received the Communication error flag remains
active for 5 minutes, but the internal counter will be reset for the next 5 minutes.