No.
Description
Name
Data format
Details
0
YFGW410.GW_STATUS
Data Status
Unsigned 16
0x0080: Good Status
1
Device
Status
Unsigned 16
Status of the field wireless device
(0: connected, 2: not connected)
2
Integer 16
Battery life (0>: days, <0: hours,
0x7FFF: external power source)
3
Unsigned 16
0 (Reserved bits)
4
5
6
7
8
9
T022FF000002A532.DEV_STATUS
Data Status
Unsigned 16
0x0080: Good Status
10
Device
Status
Unsigned 16
Status of the field wireless device
(0: connected, 2: not connected)
11
Integer 16
Battery life (0x05B4 (1460 dec))
days - normal starting point
12
Unsigned 16
Usually 0 (Reserved bits)
13
14
15
16
17
18
T022FF000002A532.UAP02.UAPMO(“STEAMTRAP_UAPMO’).DIAG_STATUS
Data Status
Unsigned 16
0x0080: Good Status
19
Diagnostic
Status
Bit String
Binary (See example #1)
20
21
T022FF000002A532.UAP02.AI_01(“PIEZO STATUS AIO”).PV
Data Status
Unsigned 16
0x0080: Good Status
22
Piezo Status
Floating
Good
Trap
Cold
Trap
Blow
Through
3F80
4000
4040
23
0000
0000
0000
24
T022FF000002A532.UAP02.AI_02(“TEMPERATURE AIO”).PV
Data Status
Unsigned 16
0x0080: Good Status
25
Temperature
Floating
32 bit hexadecimal representation
(See example #2)
26
27
T022FF000002A532.UAP02.AI_03(“TEMPERATURE SETPOINT AIO”).PV
Data Status
Unsigned 16
0x0080: Good Status
28
Temperature
Set Point
Floating
32 bit hexadecimal representation
(See example #3)
29
5.0 Modbus Register Content