background image

WARNING: 

BEFORE PROCEEDING WITH 

INSTALLATION AND OPERATION, READ ENTIRE 
MANUAL CAREFULLY. FAILURE TO DO SO CAN 
CAUSE INJURY OR PROPERTY DAMAGE

1.  working principle

Armstrong’s Brazed Plate Heat Exchanger (

abx

) consists of 

chevron plates of acid-resistant stainless steel. Every other 
plate is reversed so the ridges of the herringbone pattern 
intersect one another on adjacent plates forming a lattice 
on contact points. When these points are vacuum brazed 
together, two separate systems of channels for two media flow 
in counter-current are formed. The lattice structure causes 
vigorous turbulence, thus ensuring maximum heat transfer.

The 

abx

 is a highly efficient, corrosion-resistant, and pressure 

resistant heat exchanger. The standard 

abx

 is designed to 

meet 

435

 psi (

30

 bar), 

392°f (200°c),

 with the largest model 

capable of handling a maximum flow capacity of 

600

 gallons/

min (

42

 liter/sec). 

warning:

 The Heat Exchanger may have sharp edges. 

Exercise caution when handling

2. 

connection types 

warning:

 During operation do not exceed maximum pressure 

and temperature limits shown on the nameplate. Failure to do 
so can cause injury or property damage.

The temperature of the brazing or welding process must not 
exceed the melting point of the internal brazing material. Use 
a wet towel around the connection and the late pack to reduce 
the amount of heat transmitted to the pack during installation.

Clean the soldering assembly surface at the copper pipe and 
heat exchanger connections. Remove oil or other buildup 
with a degreasing agent. Polish the surfaces to remove 
oxide.

Apply the flux to the surface with a brush to remove and 
revent oxidation.

For refrigerant applications, use dry nitrogen gas on the 
refrigerant side.

Heat the soldering area to the soldering temperature, about 

649°c (1,200°f)

.Temperatures above this can melt the 

brazing materials and result in damage.

Keep the pipe in a fixed position and apply the filler material

3. installation guide

In order to achieve high thermal efficiency and high heat 
transfer rates, 

abx

 has to be installed in a counter flow  

direction.
Always install your 

abx

 vertically especially for a refrigerant 

system. This is done to secure the 

abx

 and keep minimum 

amount of water below the connector. 

File No:

 

113.82

Date:

 

july 15, 2020

Supersedes: 

113.82

Date:

 

october 28, 2011

ABX 

BR AZED PLATE HEAT EXCHANGERS

 

|

  

I N S TA L L AT I O N   A N D   O P E R AT I N G   I N S T R U C T I O N S

threaded connections    soldered connections 

Содержание ABX BR AZED PL ATE HEAT EXCHANGERS

Страница 1: ...rty damage The temperature of the brazing or welding process must not exceed the melting point of the internal brazing material Use a wet towel around the connection and the late pack to reduce the amount of heat transmitted to the pack during installation 1 Clean the soldering assembly surface at the copper pipe and heat exchanger connections Remove oil or other buildup with a degreasing agent Po...

Страница 2: ...the refrigeration system The following methods will prevent bphe evaporation from freezing Use brine e g glycol when evaporation temperature is close to the freezing point Low working pressure will cause low evaporation temperature If the evaporation temperature is below 32 f 0 c it will cause water to freeze Since the bottom portion has the lowest temperature it is the most likely spot for the ab...

Страница 3: ...the physical size of the particles Cleaning of fouled plate heat exchanger by back flushing will remove most of the soft debris that is blocked inside The solution used for back flushing shall be weak acids with concentration less than 5 one example is citric acid If the acidity is to high the copper and stainless steel inside the phe may be etched or corroded Before Restarting the system flush th...

Страница 4: ...ontario canada m1l 2p3 1 416 755 2291 s h a n g h a i unit 903 888 north sichuan rd hongkou district shanghai china 200085 86 0 21 5237 0909 s ão pau lo rua josé semião rodrigues agostinho 1370 galpão 6 embu das artes sao paulo brazil 55 11 4785 1330 b i r m i n g h a m heywood wharf mucklow hill halesowen west midlands united kingdom b62 8dj 44 0 8444 145 145 m a n n h e i m dynamostraße 13 68165...