background image

installation &   
operating instructions

abx

 Brazed 

Plate Heat Exchangers

2

4.  connection location

Application

fluid 1

fluid 2

Heating, Cooling

cold water
a2

a1

hot water
b1

b2

Evaporator
single refrigerant

refrigerant
a2

a1

chiller water
b1

b2

Condenser

refrigerant
a1

a2

cooling water
b2

b1

 

5.   mounting suggestions

There are four different ways to mount the 

abx

Bottom  support 

Sheet metal bracket,

Crossbar& bolts,

Stud bolts

•  All items should be supported independently.
•  Do not apply excessive forces to the fittings.
•  Except for small sized 

abx030

 model, our 

abx

 cannot be 

fastened directly to the fittings/piping.

•  Use flexible hoses or vibration dampers to reduce pulsation, 

shock or vibrations that are caused by the operating system.

6.  operating instructions

Start-Up Venting: 

During the filling process the unit must be 

vented to eliminate any trapped air. This will assure proper 
performance and longevity of the unit.

Shut Down: 

The two sides should be shut down simultaneously 

and slowly. If this is not possible the hot side should be shut 
down first. If the unit is shut down for an extended period of 
time, it must be drained and cleaned. This is especially true 
if there is a risk of frost or in the presence of any aggressive 
medium inside the heat exchanger

7.   anti-freezing protection 

methods for bphe:

Any formation of freezing or icing will damage 

bphe

 and the 

refrigeration system. The following methods will prevent 

bphe

 

evaporation from freezing:
•  Use brine (e.g. glycol) when evaporation temperature is 

close to the freezing point.

•  Low working pressure will cause low evaporation 

temperature. If the evaporation temperature is below

 32°f 

(0°c)

, it will cause water to freeze. Since the bottom portion 

has the lowest temperature, it is the most likely spot for the 

abx

 to crack.

•  To start the refrigeration system, always start the water 

pump for a few minutes and then start the compressor. To 
stop the system, always stop the compressor first and then 
stop the water pump.

Low Pressure Cut-off Switch (LP) 

A low-pressure cut-off switch should be installed with 
properly set values. When the actual evaporation pressure 
is lower than the setting value, the compressor 
will be cut off automatically.

Low temperature thermostat (LT)  

The function of thermostat is to prevent evaporation 
temperature going under 

0°c

. If evaporation temperature 

is always above 

0°c

, then water has no chance to freeze 

and expand 

Water temperature sensor 

Installation of anti-freeze 

temperature sensor neat the water outlet is another 
method to prevent the water from freezing. The suggested 
setting temperature is at 

4°c

 for buffering process

Water Flow Switch 

Installation of a water flow switch in 

the water circuit can prevent possible 

abx

 freezing up due 

to low water flow rate. Usually, low water flow rate may be 
caused by malfunction of water pump, leaking Pipes, pipe 
blockage due to pipe contamination or dirty filter.

a

b

c

d

a1

b1

b2

a2

d1

c1

c2

d2

Содержание ABX BR AZED PL ATE HEAT EXCHANGERS

Страница 1: ...rty damage The temperature of the brazing or welding process must not exceed the melting point of the internal brazing material Use a wet towel around the connection and the late pack to reduce the amount of heat transmitted to the pack during installation 1 Clean the soldering assembly surface at the copper pipe and heat exchanger connections Remove oil or other buildup with a degreasing agent Po...

Страница 2: ...the refrigeration system The following methods will prevent bphe evaporation from freezing Use brine e g glycol when evaporation temperature is close to the freezing point Low working pressure will cause low evaporation temperature If the evaporation temperature is below 32 f 0 c it will cause water to freeze Since the bottom portion has the lowest temperature it is the most likely spot for the ab...

Страница 3: ...the physical size of the particles Cleaning of fouled plate heat exchanger by back flushing will remove most of the soft debris that is blocked inside The solution used for back flushing shall be weak acids with concentration less than 5 one example is citric acid If the acidity is to high the copper and stainless steel inside the phe may be etched or corroded Before Restarting the system flush th...

Страница 4: ...ontario canada m1l 2p3 1 416 755 2291 s h a n g h a i unit 903 888 north sichuan rd hongkou district shanghai china 200085 86 0 21 5237 0909 s ão pau lo rua josé semião rodrigues agostinho 1370 galpão 6 embu das artes sao paulo brazil 55 11 4785 1330 b i r m i n g h a m heywood wharf mucklow hill halesowen west midlands united kingdom b62 8dj 44 0 8444 145 145 m a n n h e i m dynamostraße 13 68165...

Отзывы: