background image

Issue 1324

507120-01

Page 14 of 18

Maintenance

  Inspect air filters at least once a month and replace or  

clean as required. Dirty filters are the most common 

cause of inadequate heating or cooling performance. 

  Replace  disposable  filters.    Cleanable  filters  can  be 

cleaned by soaking in mild detergent and rinsing with 

cold water. 

  Install  new/clean  filters  with  the  arrows  on  the  side 

pointing in the direction of airflow.  Do not replace a 

cleanable (high velocity) filter with a disposable (low 

velocity) filter unless return air system is properly sized 

for it. 

 If

 

water should start coming from the secondary drain 

line, a problem exists which should be investigated and 

corrected.  Contact a qualified service technician.

Cabinet Insulation

 

Matte- or foil-faced insulation is installed in indoor equipment 

to provide a barrier between outside air conditions 

(surrounding ambient temperature and humidity) and the 

varying conditions inside the unit. 

 

If

 

the insulation 

barrier is damaged (wet, ripped, torn or  separated from the 

cabinet walls), the surrounding ambient air will affect the 

inside surface temperature of the cabinet. The temperature/

humidity difference between the inside and outside of the 

cabinet can cause condensation on the inside or outside 

of the cabinet which leads to sheet metal corrosion and 

subsequently, component failure. 

REPAIRING DAMAGED INSULATION 

Areas of condensation on the cabinet surface are an 

indication that the insulation is in need of repair. 

If

 

the insulation in need of repair is otherwise in good 

condition, the insulation should be cut in an X pattern, peeled 

open, glued with an appropriate all-purpose glue and placed 

back against the cabinet surface, being careful 

to not overly compress the insulation so the insulation can 

retain its original thickness.  If

 

such repair is not possible, 

replace the insulation. If

 

using foil-faced insulation, any cut, 

tear, or separations in the insulation surface must be 

taped with a similar foil-faced tape. 

Figure 13

Repairing Insulation

Do not operate system without a filter.  A filter is 

required to protect the coil, blower, and internal parts 

from excessive dirt and dust.  The filter is placed in the 

return duct by the installer.

  

IMPORTANT

DAMAGED INSULATION MUST BE REPAIRED OR 

REPLACED

 before the unit is put back into operation.  

Insulation loses its insulating value when wet, damaged, 

separated or torn.

  

IMPORTANT

Содержание BCE3M 18

Страница 1: ...Condensate Drain 7 Duct Systems and Filters 8 Connecting Refrigerant Lines 9 Sealing the Unit 9 Electrical Connections 10 Airflow Cooling Blower Speed 12 Check Out Procedures 13 Operation13 Maintenan...

Страница 2: ...9 12 1 4 311 18 7 8 479 5 3 4 146 16 7 8 429 17 3 4 451 17 432 19 7 8 505 20 3 4 527 19 3 8 492 5 1 2 140 43 1092 18 1 2 470 22 559 6 152 16 406 5 1 2 140 13 1 2 343 17 3 4 451 17 432 16 1 2 419 20 3...

Страница 3: ...space routing requirements for refrigerant line condensate disposal filters duct system wiring and accessibility for service Refer to the air handler rating plate on the air handler for specific infor...

Страница 4: ...s are provided for electrical wiring entrance For ease in installation it is best to make any necessary coil configuration changes before setting air handler in place For all performance testing units...

Страница 5: ...ntal configuration is shown in Figure 3 5 If the unit is suspended the entire length of the cabinet must be supported If you use a chain or strap use a piece of angle iron or sheet metal attached to t...

Страница 6: ...ugged Remove the plugs from the front drain pan ports 5 Re install modified coil drain pan assembly in air handler in the same orientation as before Figures 6 and 7 Figure 6 Install Main Drain Pan Mou...

Страница 7: ...ure 9 On units of this type where the blower draws rather than blows air through the coil traps must be installed in the condensate drain lines primary and auxiliary if used Traps prevent the blower f...

Страница 8: ...he drain pan to allow complete drainage of the pan NOTE Horizontal runs must have an anti siphon air vent standpipe installed ahead of the horizontal run See Figure 9 An extremely long horizontal run...

Страница 9: ...oid damaging the rubber grommets in the cabinet while brazing slide the rubber grommets over the refrigerant lines until they are away from the heat source 5 Braze using an alloy of silver or copper a...

Страница 10: ...t all power supplies 2 Remove the air handler access panel 3 Route the field supply wires to the air handler electrical connection box 4 Use UL listed wire nuts to connect the field supply conductors...

Страница 11: ...Page 11 of 18 Issue 1324 507120 01 Figure 12 Low Voltage Connections 3 Speed PSC Motor...

Страница 12: ...rom the 4 pin blower motor connector NOTE Reuse the factory installed plastic cap on whichever wire is not used 6 Replace all panels 7 Reconnect power CHANGE BLOWER SPEED NOTE Refer to wiring diagram...

Страница 13: ...elay coil and then the indoor blower relay energizes The normally open contacts close causing the indoor blower motor to operate The circuit between R and Y is completed closing the circuit to the con...

Страница 14: ...emperature of the cabinet The temperature humidity difference between the inside and outside of the cabinet can cause condensation on the inside or outside of the cabinet which leads to sheet metal co...

Страница 15: ...Page 15 of 18 Issue 1324 507120 01 Start Up and Performance Checklist Horizontal Configuration Figure 14...

Страница 16: ...Issue 1324 507120 01 Page 16 of 18 Figure 15 Start Up and Performance Checklist Upflow Configuration...

Страница 17: ...rnish the following information a complete model and serial number b proof of required periodic maintenance installation date and location and c an accurate description of the problem WARRANTY LIMITAT...

Страница 18: ...odification change or alteration of the unit except as expressly directed in writing by Allied Air 4 Improper use accident neglect or unreasonable use or operation of the unit including operation of e...

Отзывы: