background image

Issue 1324

507120-01

Page 4 of 18

Installation Clearances

NON-DUCTED RETURN CLOSET INSTALLATION

The air handler can be installed in a closet with a false bot-

tom to form a return air plenum. It may also be installed with 

a return air plenum under the air handler.

Louvers or return air grilles are field supplied.  Local codes 

may limit application of systems without a ducted return to 

single story buildings.

When these unit are installed in a closet with a louvered 

return opening, the minimum open area for the louvers will 

be:

  320 square inches for -018 and -024 models;

  360 square inches for -030 and -036 models;

  450 square inches for -042 thru -060 models.

If the free area is not known, assume a 25% free area for 

wood or a 75% free area for metal louvers or grilles. Using 

the louver dimensions and the 25% or 75% assumption, 

determine if the open area meets the minimum open area 

listed above.

If a return air plenum is used, the return air grille should be 

immediately in front of the opening in the plenum to allow 

for the free flow of return air.  When not installed in front of 

the opening, there must be adequate clearance around the 

air handler to allow for the free flow of return air.

These 

units  are  factory  assembled  and  configured  for 

installation in upflow or horizontal left hand air discharge 

applications.

Each unit consists of a blower assembly, refrigerant coil, and 

controls, in an insulated galvanized steel factory finished 

enclosure. Knockouts are provided for electrical wiring 

entrance.

For ease in installation, it is best to make any necessary coil 

configuration changes before setting air handler in place.

For all performance testing, units must be tested in the 

upflow orientation with the horizontal drain pan removed.

Refrigerant Metering Device

These units are equipped with a orifice metering device.

Upflow Application

1.   The air handler must be supported on the bottom only 

and set on solid floor or field supplied support frame. 

Securely attach the air handler to the floor or support 

frame.

2.   If installing a unit in an upflow application, remove the 

horizontal drain pan. 

  

IMPORTANT:  

The horizontal drain pan is not required 

in upflow air discharge installations; its removal provides 

the best efficiency and air flow.

 

3.    Place the unit in the desired location and level it. Connect 

return and supply air plenums as required using sheet 

metal screws. 

4.  Install units that have no return air plenum on a stand 

that is at least 14” from the floor.  This will allow proper 

air return. 

INSTALLATION

General Information

Horizontal Applications

Figure 1

Upflow Configuration

Improper installation, adjustment, alteration, service 

or maintenance can cause property damage, personal 

injury or loss of life. Installation and service must be 

performed by a qualified installer or service agency.

  

WARNING

When removing the coil, there is possible danger of 

equipment  damage  and  personal  injury.  Be  careful 

when removing the coil assembly from a unit installed 

in right- or left-hand applications. The coil may tip into 

the drain pan once it is clear of the cabinet. Support the 

coil when removing it.

  

IMPORTANT

Содержание BCE3M 18

Страница 1: ...Condensate Drain 7 Duct Systems and Filters 8 Connecting Refrigerant Lines 9 Sealing the Unit 9 Electrical Connections 10 Airflow Cooling Blower Speed 12 Check Out Procedures 13 Operation13 Maintenan...

Страница 2: ...9 12 1 4 311 18 7 8 479 5 3 4 146 16 7 8 429 17 3 4 451 17 432 19 7 8 505 20 3 4 527 19 3 8 492 5 1 2 140 43 1092 18 1 2 470 22 559 6 152 16 406 5 1 2 140 13 1 2 343 17 3 4 451 17 432 16 1 2 419 20 3...

Страница 3: ...space routing requirements for refrigerant line condensate disposal filters duct system wiring and accessibility for service Refer to the air handler rating plate on the air handler for specific infor...

Страница 4: ...s are provided for electrical wiring entrance For ease in installation it is best to make any necessary coil configuration changes before setting air handler in place For all performance testing units...

Страница 5: ...ntal configuration is shown in Figure 3 5 If the unit is suspended the entire length of the cabinet must be supported If you use a chain or strap use a piece of angle iron or sheet metal attached to t...

Страница 6: ...ugged Remove the plugs from the front drain pan ports 5 Re install modified coil drain pan assembly in air handler in the same orientation as before Figures 6 and 7 Figure 6 Install Main Drain Pan Mou...

Страница 7: ...ure 9 On units of this type where the blower draws rather than blows air through the coil traps must be installed in the condensate drain lines primary and auxiliary if used Traps prevent the blower f...

Страница 8: ...he drain pan to allow complete drainage of the pan NOTE Horizontal runs must have an anti siphon air vent standpipe installed ahead of the horizontal run See Figure 9 An extremely long horizontal run...

Страница 9: ...oid damaging the rubber grommets in the cabinet while brazing slide the rubber grommets over the refrigerant lines until they are away from the heat source 5 Braze using an alloy of silver or copper a...

Страница 10: ...t all power supplies 2 Remove the air handler access panel 3 Route the field supply wires to the air handler electrical connection box 4 Use UL listed wire nuts to connect the field supply conductors...

Страница 11: ...Page 11 of 18 Issue 1324 507120 01 Figure 12 Low Voltage Connections 3 Speed PSC Motor...

Страница 12: ...rom the 4 pin blower motor connector NOTE Reuse the factory installed plastic cap on whichever wire is not used 6 Replace all panels 7 Reconnect power CHANGE BLOWER SPEED NOTE Refer to wiring diagram...

Страница 13: ...elay coil and then the indoor blower relay energizes The normally open contacts close causing the indoor blower motor to operate The circuit between R and Y is completed closing the circuit to the con...

Страница 14: ...emperature of the cabinet The temperature humidity difference between the inside and outside of the cabinet can cause condensation on the inside or outside of the cabinet which leads to sheet metal co...

Страница 15: ...Page 15 of 18 Issue 1324 507120 01 Start Up and Performance Checklist Horizontal Configuration Figure 14...

Страница 16: ...Issue 1324 507120 01 Page 16 of 18 Figure 15 Start Up and Performance Checklist Upflow Configuration...

Страница 17: ...rnish the following information a complete model and serial number b proof of required periodic maintenance installation date and location and c an accurate description of the problem WARRANTY LIMITAT...

Страница 18: ...odification change or alteration of the unit except as expressly directed in writing by Allied Air 4 Improper use accident neglect or unreasonable use or operation of the unit including operation of e...

Отзывы: