MAGE1 User Guide
22
V1.5 12-1-2022
7= 15 min
8= 30 min
9= 1 hr
10= 2 hrs
11= 6 hrs
12= 12 hrs
13= 24 hrs
2036
2035
4
Longint
0
0
1
0
Datalogger
Delete
0= OFF,
1= ON
R/W
Measurement
0 = Stop
– the unit shows actual flow, but the totalizers are stopped
1 = Running
– totalizers are active. Default Stop
Air Detector
–
this option allows selecting empty pipe check. Default ON.
Air Constant
– constant value to determine the Empty pipe detection limit. Default 188
Real value = Actual value / 1000
Samples per Avg.
– the number of samples that the flowmeter will use for calculation of its displayed average
flow value. Default 3
Low Flow Cutoff
– this function serves to set the minimum flow the flowmeter will react on. Default 2%
Invert Flow
– this function serves to change the direction of the flow. Default OFF
Date Settings
- date write in BCD format YYYYMMDD (ie 25.03.2010 = (hex)0x20100325)
Time Settings
- time write in BCD format HHMMSS (ie 08:33:15 = (hex)0x00083315)
Modbus Slave Address
– Modbus device address. Default 1
Modbus Baudrate
–
setup communication speed. Default 9600
Modbus Parity
– setup communication parameters. Default none, 1 stopbit
Always on
– set to 0 always
Current Min
– Max
– Setup of the current output range,
corresponds to the actual flow-rate within given range
Flow Min
– Max
– Setup of measurement flow-range
Real value = Actual value / 1000 (only positive values)
min
max
max
min
Flow
Current