ADrive
53
1.1
- 1.4 – High Speed / Middle Speed / Inspection Speed / Low Speed
(V3, V2, V1, V0)
The speed which is selected by the V3, V2, V1, V0 input terminals of the inverter. In a case
of more than one speed inputs applied the higher one is activated. If the speed control inputs are
driven by relays high speed and low speed signal should be applied together. Otherwise because
of the relay delays, wrong speed inputs may be perceived at speed changes especially for
distance controlled stops it is important that there must be no delays at speed transitions.
1.5 – Acceleration
(PA: 0.10 m/s² – 5.00 m/s²)
The acceleration of the elevator. As the acceleration increased, the speed up time decreases.
If decreased the speed up time increases.
1.6-Acceleration Begin Soften
(S1: 0.10 – 5 .00 m/s³)
The acceleration of the elevator is not started directly with the parameter PA. By increasing
the acceleration smoothly with parameter S1, sharp changes in the acceleration are prevented.
Consequently the acceleration is felt less by the passenger.
1.7-Acceleration end soften
(S2: 0.10 – 5 .00 m/s³)
At the end of acceleration while passing to constant speed the acceleration is decreased
smoothly to prevent sharp changes in the acceleration. Consequently the acceleration is felt less
by the passenger.
1.8-Slowing Distance
(X_SLW: 10 - 500 cm)
If the STOPPING TYPE at Parameter 1.10 is adjusted to “STP WITH DISTANCE” while the
elevator speeds down from V3 to V0, the distance to slow down from V3 to V0 is equalized to
the value of this parameter automatically by adjusting the S ramps. No need to adjust the S3-S4
and deceleration parameters.
1.9-Stopping Distance
(X_STP: 1 – 50 cm)
If the STOPPING TYPE at Parameter 1.10 is adjusted to “STP WITH DISTANCE” the
distance from V0 to 0 speed is equalized to the value of this parameter automatically by adjusting
the S ramps. No need to adjust the S3-S4 and deceleration parameters.
1.10-Stopping Type
(STP WITH DISTNCE / WITH NA/S3/S4)
Determines that the speed transition from V3 to V0 and from V0 to 0 will be whether
according to distance or according to parameters of deceleration.
1.11-Deceleration
(NA: 0.10 – 5.00 m/s²)
The deceleration of the elevator. As the deceleration increased, the speed down time
decreases. If decreased the speed down time increases.
1.12-Deceleration Begin Soften
(S3: 0.10 – 5 .00 m/s³)
The deceleration of the elevator is not started directly with the parameter NA. By increasing
the deceleration smoothly with parameter S3, sharp changes in the deceleration are prevented.
Consequently the deceleration is felt less by the passenger.