Appendix A: Configuration presets
1X-E4 Series Installation Manual
81
NEN 2575 2E presets
Table 40: Configuration presets
Preset
43
Control panel
T wo evacuation areas
EOL type
Passive
Output type
Class B
Evacuation sounder outputs
4
Fire routing outputs
3
Zone type
Odd: Automatic
Even: Manual
Table 41: Inputs and outputs
Input/Output Standard
EN 54-13
INPUT1
Fire routing inhibit delay
Fire routing acknowledge type1
INPUT2
Delays off
Fault warning open supervision
OUT1
Sounder circuit (activated by a fire
alarm in zone 1 or 2)
Sounder circuit (activated by a fire
alarm in zone 1 or 2)
OUT2
Sounder circuit (activated by a fire
alarm in zone 1 or 2)
OUT3
Sounder circuit (activated by a fire
alarm in zone 3 or 4)
Sounder circuit (activated by a fire
alarm in zone 3 or 4)
OUT 5
Fire routing ( activated by a automatic
fire alarm device)
Fire routing (activated by automatic or
manual fire alarm device)
OUT 6
Fire routing (activated by a manual fire
alarm device)
NEN 2575 1E presets
Table 42: Configuration presets
Preset
45
Control panel
One evacuation area
EOL type
Passive
Output type
Class B
Evacuation sounder outputs
4
Fire routing outputs
2
Zone type
Odd: Automatic
Even: Manual
Содержание 1X-E4 Series
Страница 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Страница 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Страница 84: ...Chapter 5 Technical specifications 78 1X E4 Series Installation Manual Figure 21 Cabinet without cover ...
Страница 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Страница 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...