Chapter 2: Installation
1X-E4 Series Installation Manual
15
Connecting supervised outputs
The evacuation control panel has six outputs, marked OUT1 through OUT6.
The outputs are supervised for open and short circuit faults.
Output class
The evacuation control panel outputs can be configured for Class A or Class B
operation, depending on the supervision mode required. The default output
configuration is Class B.
Table 9: Output classes and EN 54-13 supervision
Output class
EN 54-13 supervision
Description
Class B (default)
Disabled
For installations not requiring EN 54-13
compliance
Class A
Enabled
For installations requiring EN 54-13
compliance
For more information, see “EN 54-13 supervision mode” on page 35.
Output functionality
The function of each output is defined by the panel operating mode and output
class configuration (the default is Class B). All outputs are overload protected.
Table 10: Class B output functionality (default)
Operating mode OUT1
OUT2
OUT3
OUT4
NEN 2575 with
four evacuation
areas
Evacuation
sounders for
zone 1
Evacuation
sounders for
zone 2
Evacuation
sounders for
zone 3
Evacuation
sounders for
zone 4
NEN 2575 with
two evacuation
areas
Evacuation
sounders for
zone 1 or zone 2
Evacuation
sounders for
zone 1 or zone 2
Evacuation
sounders for
zone 3 or zone 4
Evacuation
sounders for
zone 3 or zone 4
NEN 2575 with
one evacuation
area
Evacuation
sounders for any
zone
Evacuation
sounders for any
zone
Evacuation
sounders for any
zone
Evacuation
sounders for any
zone
Содержание 1X-E4 Series
Страница 1: ...1X E4 Series Installation Manual P N 501 415403 1 50 ISS 13JUN22 ...
Страница 76: ...Chapter 4 Maintenance 70 1X E4 Series Installation Manual ...
Страница 84: ...Chapter 5 Technical specifications 78 1X E4 Series Installation Manual Figure 21 Cabinet without cover ...
Страница 94: ...Appendix A Configuration presets 88 1X E4 Series Installation Manual ...
Страница 98: ...Appendix B Regulatory information 92 1X E4 Series Installation Manual ...