3
commissioning
Test function and combustion analysis
The boiler has two pressure taps to measure the combustion gas
temperature, the combustive air and the concentrations of O
and CO on the outside of the flue gas header.
to access these pressure taps, unscrew the screw which holds the
blanking cover and its seal together.
Checking the gas setting
To carry out analyses of combustion, the test function must be
activated.
Maximum gas flow combustion analysis
Activate the test function at the maximum heating power t
--
Wait for the boiler to stabilise before carrying out the combustion
analyses. Check the CO value according to the table below.
Important: do not remove silencer
22
N.B.: when the front combustion chamber panel is open, the
CO2 value drops by 0.3%.
If the values taken differ from the table, adjust the gas valve fol-
lowing the procedure described below.
Adjust the CO content to
± 0.2
by turning setting screw
50
(
2.5
mm allen key
)
- tighten to lower the CO value
- unscrew to increase the CO value
Set the content by turning the screw about a 1/4 of a turn then
wait after each change for approximately 1 minute for the CO
value to stabilise, then repeat.
Minimum gas flow combustion analysis
Activate the cleaning function at minimum power in either
heating or domestic hot water production.
Wait for the boiler to stabilise before carrying out the combustion
analyses. Check the CO value according to the table above.
Important: do not remove silencer
N.B.: when the combustion chamber is open, the CO2 value
drops by 0.3%.
If the values taken differ from the table, adjust the gas valve fol-
lowing the procedure described below.
To adjust the CO value, remove cap
2
, adjust the CO content to
± 0.2
by turning setting screw
51
(
4 mm allen key
)
- unscrew to lower the CO value
- tighten to increase the CO value
Set the content by turning the screw about a 1/4 of a turn then
wait after each change for approximately 1 minute for the CO
value to stabilise, then repeat.
Once the settings and analyses are complete, exit test mode, and
reposition the blanking cover and its seal correctly.
Maximum or mini-
mum CO
18 kW
4 kW
30 kW
CO
(%)
G0
9.0 ± 0.
9.0 ± 0.
9.0 ± 0.
G31
10.7 ± 0.
10.7 ± 0.
10.0 ± 0.
8
50
Only a 2.5 mm allen
key must be used. Do
not use a screwdriver
2
Only a 4 mm
allen key must be
used. Do not use a
screwdriver
51
Test function
The PCB allows the appliance to be forced to minimum or
maximum power.
Activate the cleaning function by pressing the
Reset
button for
5 seconds, the boiler switches to maximum heating power, the
following appears on the display:
To select the test function at maximum domestic hot water,
press the
button, the following appears on the display :
To select the function at minimum domestic hot water, press
the
button, the following appears on the display :
The function is automatically deactivated after 10 minutes or by
pressing the
Reset
button.
Note: the appliance can be forced to minimum or maximum
power from menu 7 (see the section on the display - setting -
diagnostics menu).
Silencer