CH anti cycling delay setting :
If you would like to change the setting of CH anti cycling delay, if you want 3 mn ,please proceed as follow :
(note : the factory setting is 2 mn 30 seconds and the following explanation refer to menu 4 section 8)
Display
17. Adjustements and Setting
(continued)
1
5 ”
2
x 3
1
2
or
3
3
4
4
Switch to installer mode, press button
and
for 5 seconds, the
display shows :10=0 if there is no
default in the default register.
Press 3 times on menu button
to
gain access to menu 4, the display
shows : 40=0 or 40=1
Change for section 8 (CH anti cycling
delay), press on button
side
times , the display shows :48=2.5
(factory setting 2 mn 30 s)
4 = menu 4
8 = section 8
2.5 = 2,5 mn (2 mn 30 secondes)
Press on setting button
one time,
the 3rd and 4th digits flash together,
Then press on
to change the CH
anti cycling delay, the display shows :
48=3.0 press on setting button
to confirm the value. The display
stops flashing.
Setting procedure is finished.
To exit from setting mode, leave the
boiler for approx. 1 minute then the
computer will switch back to user
mode.
After programming please close the
door P (fig. 48)