DECLARATION OF CONFORMITY
This product is marked as it satisfies Directives:
– Low voltage no. 2006/95/CE.
– Electromagnetic compatibility no. 89/336 ECC, 92/31 EEC and 93/68 EEC.
This declaration will become void in case of misuse and/or non observance though partial of manufacturer's installation
and/or operating instructions.
Power Supply:
230V / 1 / 50Hz
1.Standard screwdriver
2.Phillips head screwdriver
3.Knife or wire stripper
4.Tape measure
5.Level
6.Sabre saw or key hole saw
7.Hacksaw
8. Core bits ø 8
1
9.Hammer
10.Drill
11. Tube cutter
12.Tube flaring tool
13.Torque wrench
14.Adjustable wrench
15.Reamer (for reburring)
16.Hex. key
Tools required for installation (not supplied)
Model Combinations
Combine indoor and outdoor units only as listed below.
Indoor Units
Outdoor Units
AWI826HL
AEI726SH(N)
AWI826HLB
AWI8826HL
AEI826SH
AWI8826HLB
AWI835HL
AEI735SH(N)
AWI835HLB
AWI8835HL
AEI835SH
AWI8835HLB
37.4255.033.0 06/2008
INSTALLATION INSTRUCTIONS
- Split system air conditioner -
P
GR
F-GAS Regulation (EC) No. 842/2006
Do not vent R410A into atmosphere: R410A is a
fluorinated greenhouse gas, covered by Kyoto Protocol,
with a Global Warming Potential (GWP) = 1975.
OPERATING LIMITS
L
Cooling Maximum conditions
Outdoor temperature
:
43°C D.B.
Room temperature :
32°C D.B. / 23°C W.B.
L
Cooling Minimum conditions
Outdoor temperature
: –15°C D.B.
19°C D.B. (AEI 726-735SH)
Room temperature :
10°C D.B. / 6°C W.B.
L
Heating Maximum conditions
Outdoor temperature
:
24°C D.B. / 18°C W.B.
Room temperature :
27°C D.B.
L
Heating Minimum conditions
Outdoor temperature
:
–15°C D.B.
–8°C D.B. / –9°C W.B.
(AEI 726-735SH)
Room temperature :
5°C D.B.