5-2 Cool Mode Operation
In Cooling Mode, the operation of the compressor (CM), Outdoor Fan (FMO) and Indoor Fan (FMI) are
determined by:
1) the difference between the room air temperature (RAT) and the set point temperature (SPT)
2) the protection level at which the system is operating
NOTES
In addition to the temperature difference of above, the operation of the main components (CM, FMO,
FMI) is also controlled by protection function.
The minimum off time of compressor is 3 minutes.
The indoor fan can change speed only after it has operated at the same speed for 30 sec if in AUTO
and 1 sec for the other settings (High, Med, Low).
5-3 Heat Mode Operation
The Heating mode operation is similar to the Cooling mode operation. The CM, FMO and FMI are controlled
by the same parameters.
NOTES
1. After the CM has stopped, the FMI runs for 30s in order to purge heat from the indoor coil.
2. The FMI will not be turned on until the indoor coil temperature is warm enough to prevent the supply of
cold air (see COLD DRAFT PREVENTION feature for details).
The indoor fan can change speed only after it has operated at the same speed for 30 sec if in AUTO and
1 sec for the other settings (High, Med, Low).
16
Содержание AWI726HL
Страница 9: ...2 DIMENSIONAL DATA AWI726HL I AWI735HL I 9 ...
Страница 10: ...2 DIMENSIONAL DATA REF09HI REF12HI 10 ...
Страница 13: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagrams AWI726HL I AWI735HL I 13 ...
Страница 14: ...REF09HI REF12HI 14 ...
Страница 29: ...6 3 SYSTEM DOES NOT RUN 29 ...
Страница 31: ...6 4 OUTDOOR UNIT DOES NOT RUN AND NO FAULT IS DISPLAIED 6 5 ONLY OUTDOOR UNIT IS OFF 31 ...
Страница 32: ...6 6 OUTDOOR UNIT FAULT SIGNALING 32 ...
Страница 34: ...34 ...
Страница 35: ...6 8 NOISY PROBLEM 35 ...
Страница 36: ...7 CHECKING ELETRICAL COMPONENTS 7 1 36 ...
Страница 37: ...7 2 37 ...
Страница 38: ...Via Varese 90 21013 Gallarate Va Italy Tel 39 0331 755111 Fax 39 0331 776240 www argoclima it ...