5-10 Protection operations on outdoor unit
5-10.1 Overheating
During cooling operation as soon as the outdoor coil temperature (OCT) increases, compressor speed
is reduced in order to avoid heat exchanger overheating. System stops compressor operation when OCT reaches 60 °C
5-10.2 Compressor discharge temperature
During operation, as soon as the discharge temperature increases, (CDT) compressor speed is reduced
in order to avoid overheating of the motor. Compressor is stopped when CDT reaches 105°C
5-10.3 Compressor power-module overheating
The module temperature, detected by a built-in thermistor, is always monitored by the control system and kept
operating in a safe area. If temperature exceeds 100°C, operation is automatically stopped.
5-10.4 Outdoor fan power-module overheating
The module temperature, detected by a built-in thermistor, is always monitored by the control system and kept
operating in a safe area. If temperature exceeds 100°C, operation is automatically stopped.
5-10.5 Compressor power-module overcurrent
In case of current driven to each motor phase greater than 10 A operation is automatically stopped
5-10.6 Outdoor fan power-module overcurrent
In case of current driven to each motor phase greater than 400mA operation is automatically stopped
20
Содержание AWI726HL
Страница 9: ...2 DIMENSIONAL DATA AWI726HL I AWI735HL I 9 ...
Страница 10: ...2 DIMENSIONAL DATA REF09HI REF12HI 10 ...
Страница 13: ...4 ELECTRICAL DATA 4 1 Electric Wiring Diagrams AWI726HL I AWI735HL I 13 ...
Страница 14: ...REF09HI REF12HI 14 ...
Страница 29: ...6 3 SYSTEM DOES NOT RUN 29 ...
Страница 31: ...6 4 OUTDOOR UNIT DOES NOT RUN AND NO FAULT IS DISPLAIED 6 5 ONLY OUTDOOR UNIT IS OFF 31 ...
Страница 32: ...6 6 OUTDOOR UNIT FAULT SIGNALING 32 ...
Страница 34: ...34 ...
Страница 35: ...6 8 NOISY PROBLEM 35 ...
Страница 36: ...7 CHECKING ELETRICAL COMPONENTS 7 1 36 ...
Страница 37: ...7 2 37 ...
Страница 38: ...Via Varese 90 21013 Gallarate Va Italy Tel 39 0331 755111 Fax 39 0331 776240 www argoclima it ...