26
13
NTT A (Wide Tube
Temperature)
sensor fault.
Compressor and fan
are stopped.
The system restarts
as soon as the
sensor is repaired.
Sensor out of order or
disconnected (check
wiring diagram).
Reconnect or replace the sensor.
14
NTT B (Wide Tube
Temperature)
sensor fault.
Compressor and fan
are stopped.
The system restarts
as soon as the
sensor is repaired.
Sensor out of order or
disconnected (check
wiring diagram).
Reconnect or replace the sensor.
15
or
100
Wrong selection of
indoor units
combined with the
outdoor unit.
Compressor and fan
are stopped.
The selection of the
indoor units connected
to the outdoor unit is
not allowed.
Check for the allowed combinations.
Choose a correct indoor-outdoor units
combination.
101
Test Mode error (at
factory only).
Compressor and fan
are stopped.
Unit is running the
factory test mode
routine.
Cycle the power supply to the normal
functioning.
Содержание AEI1G 42 EMX
Страница 27: ...27 13 Component replacement FRONT RIGHT LEFT AND REAR PANEL ...
Страница 28: ...28 ...
Страница 29: ...29 CONTROL AND EXPANSION BOARD remove the right the left the front and the rear panel ...
Страница 30: ...30 ...
Страница 31: ...31 ...
Страница 32: ...32 COMPRESSOR remove the right the left the front and the rear panel ...
Страница 33: ...33 EXPANSION VALVE remove the right the left the front and the rear panel ...
Страница 34: ...34 FAN MOTOR remove the right the left the front and the rear panel ...
Страница 36: ...36 15 Labels Energy labels AEI1G 42 EMX ...
Страница 37: ...37 AEI1G 50 EMX Energy labels ...
Страница 38: ...38 Rating labels ...
Страница 39: ... ARGOCLIMA SPA Via Alfeno Varo 35 Alfianello BS Italy ...