The are two possible defrost type:
-
hot gas bypass defrost
-
reverse cycle defrost
If jumper JP2 is closed, the unit will automatically decide which type of defrost is necessary to run.
If jumper JP2 is open, the hot gas bypass defrost is disabled and the defrost cycles will be done only
with the reverse cycle method.
The hot gas bypass defrost is also disabled if OAT falls below 2°C.
When defrost is active:
-
4-way valve is deactivated (reverse cycle type) or defrost valve is opened (hot gas bypass type)
-
Compressor runs at a fixed speed (if no protection is active)
-
EEVs are open at a fixed value
-
Fan is off
When defrost ends:
-
4-way valve is reactivated (reverse cycle type) or defrost valve is closed (hot gas bypass type)
-
EEV are opened at a fixed value for 5 minutes
Содержание AEI1G 42 EMX
Страница 27: ...27 13 Component replacement FRONT RIGHT LEFT AND REAR PANEL ...
Страница 28: ...28 ...
Страница 29: ...29 CONTROL AND EXPANSION BOARD remove the right the left the front and the rear panel ...
Страница 30: ...30 ...
Страница 31: ...31 ...
Страница 32: ...32 COMPRESSOR remove the right the left the front and the rear panel ...
Страница 33: ...33 EXPANSION VALVE remove the right the left the front and the rear panel ...
Страница 34: ...34 FAN MOTOR remove the right the left the front and the rear panel ...
Страница 36: ...36 15 Labels Energy labels AEI1G 42 EMX ...
Страница 37: ...37 AEI1G 50 EMX Energy labels ...
Страница 38: ...38 Rating labels ...
Страница 39: ... ARGOCLIMA SPA Via Alfeno Varo 35 Alfianello BS Italy ...