Components operation
Compressor
The compressor runs if the following conditions are met:
-
At least 3 minutes have passed since the power supply was switched on
-
At least 3 minutes have passed since the compressor was stopped
-
At least 6 minutes have passed since the previous compressor start
-
There is no active alarm on the outdoor and indoor units
-
There is no active protection
-
There is a capacity demand in the rooms
Compressor stops if:
-
At least 3 minutes have passed since compressor start
-
There is no capacity demand
or if:
-
At least 3 minutes have passed since compressor start
-
Protection level is too high
or if there is any alarm active.
Fan
The fan runs only when the compressor is running and starts right after the compressor.
The fan can also run without compressor in the following conditions:
-
Overheating on the outdoor heat exchanger (cooling or dry mode)
-
Overheating on the power electronics
Electronic Expansion Valve (EEV)
EEVs are managed based on the system conditions to meet the maximum efficiency point of operation
and to guarantee a safe operation of the system.
In cooling mode, EEVs of indoor units without a capacity demand will be closed.
In heating mode, EEVs of indoor unit without a capacity demand will stay open at a minimum value to
allow the refrigerant to flow back to the compressor. This can cause a small heat loss in the heat
ecxchanger of the off units.
Every time power supply is switched on, or once per day if compressor is not running, EEV runs a reset
cycle necessary to find the correct position of the valve. During this reset cycle, EEV is completely closed
and then reopened to a fixed value.
4-way valve
4-way valve is activated when:
-
System is in heating mode
4-way valve is deactivated when:
-
System is in cooling, dry or fan only mode
-
System is off
-
Defrost is active
Содержание AEI1G 42 EMX
Страница 27: ...27 13 Component replacement FRONT RIGHT LEFT AND REAR PANEL ...
Страница 28: ...28 ...
Страница 29: ...29 CONTROL AND EXPANSION BOARD remove the right the left the front and the rear panel ...
Страница 30: ...30 ...
Страница 31: ...31 ...
Страница 32: ...32 COMPRESSOR remove the right the left the front and the rear panel ...
Страница 33: ...33 EXPANSION VALVE remove the right the left the front and the rear panel ...
Страница 34: ...34 FAN MOTOR remove the right the left the front and the rear panel ...
Страница 36: ...36 15 Labels Energy labels AEI1G 42 EMX ...
Страница 37: ...37 AEI1G 50 EMX Energy labels ...
Страница 38: ...38 Rating labels ...
Страница 39: ... ARGOCLIMA SPA Via Alfeno Varo 35 Alfianello BS Italy ...