18
9
Protections
The unit is equipped with an automatic system of protections. These protections, if active, will limit the
speed of the compressor in order to run the system in a safe operating area.
Protections, when active, reduce the speed of the compressor linearly down to its minimum speed. If the
level of protection is too high, compressor is stopped until no protection will be active.
Overheating on outdoor unit heat exchanger
This protection checks the temperature on the outdoor coil (OCT) to avoid overheating and overpressure
of the heat exchanger.
This protection is active only in cooling or dry mode and starts to limit the compressor speed when OCT
is higher than 55°C.
Overheating on indoor units heat exchanger
This protection checks the temperature on the indoor coils (ICT) to avoid overheating and overpressure
of the heat exchanger and reduces the high pressure noise inside the indoor unit.
This protection is active only in heating mode and starts to limit the compressor speed when ICT is
higher than 48°C(*).
Notes:
-
(*) ICT threshold may vary depending on the model of the indoor unit
-
If High Power option is active, protection will start at higher values of ICT, increasing the heating
capacity
Freeze-up on indoor unit heat exchanger
This protection checks the temperature on the indoor coil (ICT) to avoid freezing of the indoor unit heat
exchanger.
This protection is active only in cooling or dry mode and starts to limit the compressor speed when ICT
is lower than 8°C.
Furthermore, if the unit is stopped because of this protection, in order to drip away all the condensed
water on the indoor coil, it will not restart until ICT is higher than 8°C.
Overheating on the compressor
This protection checks the compressor’s discharge temperature (CDT) to avoid overheating of the
compressor.
This protection is always active and starts to limit the compressor speed when CDT is higher than 80°C.
Overheating on the power electronic
This protection checks the temperature of the electronic power module connected to the heatsink. The
temperature sensor is built into the module, so there is no direct access to it.
This protection is always active and starts to limit the compressor speed when power electronic
temperature is higher than 90°C.
Overpower consumption from the power supply
This protection checks the power consumption of the outdoor unit (but not of the indoor unit) to avoid
an excessive power consumption than can damage the pcb and the unit.
This protection is always active and limits the compressor speed to keep the outdoor unit power
consumption below 1800W.
Overcurrent of the compressor
This protection checks the current consumption of the compressor to avoid damage to the compressor
and to the pcb.
This protection is always active and limits the compressor speed to keep the current consumption of the
compressor below 11A.
Содержание AEI1G 42 EMX
Страница 27: ...27 13 Component replacement FRONT RIGHT LEFT AND REAR PANEL ...
Страница 28: ...28 ...
Страница 29: ...29 CONTROL AND EXPANSION BOARD remove the right the left the front and the rear panel ...
Страница 30: ...30 ...
Страница 31: ...31 ...
Страница 32: ...32 COMPRESSOR remove the right the left the front and the rear panel ...
Страница 33: ...33 EXPANSION VALVE remove the right the left the front and the rear panel ...
Страница 34: ...34 FAN MOTOR remove the right the left the front and the rear panel ...
Страница 36: ...36 15 Labels Energy labels AEI1G 42 EMX ...
Страница 37: ...37 AEI1G 50 EMX Energy labels ...
Страница 38: ...38 Rating labels ...
Страница 39: ... ARGOCLIMA SPA Via Alfeno Varo 35 Alfianello BS Italy ...