Duct Type Unit
24
2.2.3.5 Thermal Insulation of Pipe Joint (Only for indoor unit)
Stick coupler heat insulation (large and small) to the place where connecting
pipes.
2.2.4 Connection Pipe Vacuum Pumping and Leak Detection
2.2.4.1 Vacuum Pumping
NOTE!
Make sure the outlet of vacuum pump is away from fire source and is
well-ventilated.
(1) Remove the caps of the liquid valve, gas valve and also the service port.
(2) Connect the hose at the low pressure side of the manifold valve assembly
to the service port of the unit’s gas valve, and meanwhile the gas and
liquid valves should be kept closed in case of refrigerant leak.
(3) Connect the hose used for evacuation to the vacuum pump.
(4) Open the switch at the lower pressure side of the manifold valve
assembly and start the vacuum pump. Meanwhile, the switch at the high
pressure side of the manifold valve assembly should be kept closed,
otherwise evacuation would fail.
(5) The evacuation duration depends on the unit’s capacity, generally.