Outdoor unit heating capacity correction cofficient during of frosting/defrosting (RH approximately 85%)
Outdoor intake air
temperature °C WB
-20 -15 -10 -9 -8 -7 -6 -5 -4 -3 -2 -1
0
1
2
3
4
5
6
Correction coef? cient
1.0 1.0 0.97 0.96 0.96 0.95 0.94 0.91 0.89 0.88 0.87 0.87 0.87 0.88 0.89 0.91 0.92 0.95 1.0
To calculate the heating capacity with consideration for frosting/defrosting operation, multiply the heating capacity
found from the capacity graph by the correction coefficient from the table above.
140
40
60
80
100
120
140
120
100
80
60
22WB
19WB
16WB
16WB
22WB
19WB
-15
15
5
3
5
4
5
2
5
5
-
120
40
60
80
100
120
100
80
60
40
0
1
-
0
2
-
5
1
-
10
-5
0
16 °C
20 °C
24 °C
16 °C
20 °C
24 °C
5
AES100PIH3E, AES125PIH3E (For 50 Hz and 60 Hz)
SPW-C366VEHN, C486VEHN, C606VEHN (For 50 Hz and 60 Hz)
AES100PIH3E
AES125PIH3E
Cooling capacity ratio (maximum capacity)
Heating capacity ratio (maximum capacity)
Input coefficient (%) Capacity coefficient (%)
Outdoor air intake temp ( °C DB)
0
2
4
6
8
10
12
2
4
6
8
10
12
14
16
Outdoor air intake temp ( °C DB)
Input coefficient (%) Capacity coefficient (%)
Outdoor air intake temp ( °C WB)
Cooling
Heating
0
20
40
60
80
100
120
140
160
180
160
180
160
180
Input coefficient (%)
0
20
40
60
80
100
120
140
Input coefficient (%)
15
Outdoor air intake temp ( °C WB)
0
2
4
6
8
10
12
14
16
18
2
4
6
8
10
12
14
16
18
20
Indoor air intake temp ( °C DB)
Indoor air intake temp ( °C DB)
Indoor air intake temp ( °C WB)
Indoor air intake temp ( °C WB)
0
Outdoor air intake temp ( °C DB)
Cooling
Heating
0
20
40
60
80
100
120
140
160
180
Input coefficient (%)
0
20
40
60
80
100
120
140
Input coefficient (%)
Outdoor air intake temp ( °C WB)
0
122%
146%
121%
146%
SM830159-06̲Elite̲PAC-i.indb 344
SM830159-06̲Elite̲PAC-i.indb 344
2012/04/27 15:22:40
2012/04/27 15:22:40