![Argo ACS100 Скачать руководство пользователя страница 26](http://html.mh-extra.com/html/argo/acs100/acs100_service-manual_2967426026.webp)
1-
23
1
Single-Type
1-1. Unit Specif cations
Ceiling-Mounted Type
ACS71PH
/
AES71PIH3E
MODEL No.
Indoor Unit
ACS71PH
Outdoor Unit
AES71PIH3E
POWER SOURCE
380 - 400 - 415 V, 3 phase, 50 Hz
PERFORMANCE
Cooling
Heating
Capacity [min~max]
kW
7.1 [2.2~8.0]
8.0 [2.2~10.0]
BTU / h
24,000 [7,500~27,000]
27,000 [7,500~34,000]
Air circulation (Hi / Me / Lo)
m
3
/ h
1,100 / 900 / 840
Moisture removal (High)
Liters / h
3.0
–
ELECTRICAL RATINGS
Voltage ratings
V
380
400
415
380
400
415
Available voltage range
V
342 - 456
342 - 456
Running amperes*
A
4.10
3.84
3.67
4.44
4.17
3.98
Max–Running amperes**
A
–
–
–
–
–
–
Power input
kW
2.35
2.55
C.O.P
W / W
3.02
3.14
Max.Starting amperes
A
–
–
–
–
–
–
FEATURES
Controls / Thermostat control
Microprocessor / I.C.thermostat
Timer
ON / OFF 72-hours
Fan speeds Indoor / Outdoor
3 and Automatic control / Variable
Airflow direction (Indoor)
Automatic (Remote control)
Air filter
Washable, easy access, long life (2,500 hr)
Remote controller (Option)
Wired: RCS-TM80BG / Wireless: RCS-TRP80BG.WL
Refrigerant control
–
Drain pump (Drain connection)
(20A, OD26mm)
Compressor
Rotary (SANYO)
Operation sound
Indoor - Hi / Me / Lo
dB-A
38 / 36 / 33
Outdoor - Hi
dB-A
47.0
49.0
Color
(Approximate value)
Indoor
Munsell 10Y 9.3 / 0.4
Outdoor
Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Indoor unit
Outdoor unit
Limit of tubing length
m (ft.)
50 (164)
Limit of tubing length at shipment
m (ft.)
3~30(10~98)
Limit of elevation difference
between the two units
m (ft.)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 15 (49)
Refrigerant tube
outer diameter
Liquid tube
mm (in.)
9.52 (3 / 8)
9.52 (3 / 8)
Gas tube
mm (in.)
15.88 (5 / 8)
15.88 (5 / 8)
Refrigerant amount at shipment
kg
–
R410A - 2.3
DIMENSIONS & WEIGHT
Indoor unit (include panel)
Outdoor unit
Unit dimensions
Height
mm (in.)
210 (8-9 / 32)
780 (30-45 / 64)
Width
mm (in.)
1,180 (46-15 / 32)
940 (37-1 / 64)
Depth
mm (in.)
680 (26-25 / 32)
340 (13-25 / 64)
Package dimensions
Height
mm (in.)
280 (11-1 / 32)
945 (37-13 / 64)
Width
mm (in.)
1,255 (49-13 / 32)
1015 (39-61 / 64)
Depth
mm (in.)
780 (30-23 / 32)
409 (16-7 / 64)
Net weight
kg (lb.)
25 (55)
65 (143)
Shipping weight
kg (lb.)
28 (62)
73 (161)
Shipping volume
m
3
(cu.ft)
0.274 (9.7)
0.392 (13.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*):
Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):
Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):
Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):
Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
SM830159-06̲Elite̲PAC-i.indb 195
SM830159-06̲Elite̲PAC-i.indb 195
2012/04/27 15:21:52
2012/04/27 15:21:52