1
1-110
Q
Q
Q
Reference diagram for snow-proof vents – 2
Space requirements for setting – (2)
The models of
AES71PIH3E
with STK-BDRE80A
[Obstacle to the front and rear of unit]
The top and both sides must remain open. Either the obstacle to the front or the obstacle to the rear
must be no taller than the height of the outdoor unit.
(1) Single-unit installation
(2) Obstacles on both sides
[Installation in front-rear rows]
The top and both sides must remain open. Either the obstacle to the front or the obstacle
to the rear must be no taller than the height of the outdoor unit.
Min. 1000
Min.
P
or more
Min.
O
or more
Min. 300
Min. 300
Min.
1000
Min.
300
Dimension Q
If a snow protection duct is attached after the unit is
installed, verify that dimension Q is 500 mm or more.
Outdoor unit
O
P
AES71PIH3E
1000 150
Min. 300
Min. 1500
Min. 2000
Min. 200
Dimension Q
If a snow protection duct is
attached after the unit is
installed, verify that dimension
Q is 500 mm or more.
SM830159-06̲Elite̲PAC-i.indb 406
SM830159-06̲Elite̲PAC-i.indb 406
2012/04/27 15:23:20
2012/04/27 15:23:20