![Argo ACS100 Скачать руководство пользователя страница 38](http://html.mh-extra.com/html/argo/acs100/acs100_service-manual_2967426038.webp)
1-
3
5
1
Single-Type
1-1. Unit Specif cations
Concealed-Duct Type
ADS125PH
/
AES125PIH3E
MODEL No.
Indoor Unit
ADS125PH
Outdoor Unit
AES125PIH3E
POWER SOURCE
380 - 400 - 415 V, 3 phase, 50 Hz
PERFORMANCE
Cooling
Heating
Capacity [min~max]
kW
12.5 [2.7~14.0]
14.0 [2.7~17.5]
BTU / h
42,500 [9,200~48,000]
48,000 [9,200~59,500]
Air circulation (Hi / Me / Lo)
m
3
/ h
1,980 / 1,560 / 1,320
Moisture removal (High)
Liters / h
6.6
–
External static pressure (High)
Pa (mmAg)
78 (8.0): at shipment, 113 (11.5): using the booster cable
ELECTRICAL RATINGS
Voltage ratings
V
380
400
415
380
400
415
Available voltage range
V
342 - 456
342 - 456
Running amperes*
A
6.94
6.56
6.28
7.06
6.66
6.37
Max–Running amperes**
A
–
–
–
–
–
–
Power input
kW
4.07
4.09
4.10
4.08
4.10
4.11
C.O.P
W / W
3.07
3.06
3.05
3.43
3.41
3.41
Max.Starting amperes
A
–
–
–
–
–
–
FEATURES
Controls / Thermostat control
Microprocessor / I.C.thermostat
Timer
ON / OFF 72-hours
Fan speeds Indoor / Outdoor
3 and Automatic control / Variable
Airflow direction (Indoor)
–
Air filter
Field supply
Remote controller (Option)
Wired: RCS-TM80BG / Wireless: RCS-BH80BG.WL
Refrigerant control
–
Drain pump (Drain connection)
Max.head 50cm above drain connection (25A, OD32mm)
Compressor
Rotary (SANYO)
Operation sound
Indoor - Hi / Me / Lo
dB-A
40 / 37 / 33, (44 / 40 / 37: using the booster cable)
Outdoor - Hi
dB-A
53.0
54.0
Color
(Approximate value)
Indoor
–
Outdoor
Munsell 1Y 8.5 / 0.5
REFRIGERANT TUBING
Indoor unit
Outdoor unit
Limit of tubing length
m (ft.)
70 (230)
Limit of tubing length at shipment
m (ft.)
5~30(16~98)
Limit of elevation difference
between the two units
m (ft.)
Outdoor unit is higher than indoor unit: 30 (98)
Outdoor unit is lower than indoor unit: 15 (49)
Refrigerant tube
outer diameter
Liquid tube
mm (in.)
9.52 (3 / 8)
9.52 (3 / 8)
Gas tube
mm (in.)
15.88 (5 / 8)
15.88 (5 / 8)
Refrigerant amount at shipment
kg
–
R410A - 3.4
DIMENSIONS & WEIGHT
Indoor unit
Outdoor unit
Unit dimensions
Height
mm (in.)
310 (12-7 / 32)
1330 (52-23 / 64)
Width
mm (in.)
1,480 (58-9 / 32)
940 (37-1 / 64)
Depth
mm (in.)
630 (24-26 / 32)
340 (13-25 / 64)
Package dimensions
Height
mm (in.)
358 (14-3 / 32)
1430 (56-19 / 64)
Width
mm (in.)
1,671 (65-25 / 32)
1015 (39-61 / 64)
Depth
mm (in.)
783 (30-26 / 32)
420 (16-17 / 32)
Net weight
kg (lb.)
47 (104)
96 (211)
Shipping weight
kg (lb.)
52 (115)
106 (234)
Shipping volume
m
3
(cu.ft)
0.468 (16.5)
0.610 (21.5)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*):
Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Full load conditions (**):
Indoor air temperature 32°C DB/23°C WB, Outdoor air temperature 43°C DB
Heating:
Rating conditions (*):
Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB
Full load conditions (**):
Indoor air temperature 24°C DB, Outdoor air temperature 24°C DB/15.5°C WB
SM830159-06̲Elite̲PAC-i.indb 255
SM830159-06̲Elite̲PAC-i.indb 255
2012/04/27 15:22:11