11
ELECTRICAL DIAGRAMS – EC FANS
- Scheme EC-3 (Image 4):
- Scheme EC-4 (Image 5):
Number Connection Function
1
24V
Voltage output 24 VDC–= 70 mA (Connect to terminal 1 of the ARFIT flow regulator to enable
operation)
2
10V
Voltage output 10 VDC - Imax = 10 mA (Terminal 5 flow regulator ARFIT)
3
GND
Connection for control interface (terminal 3 flow regulator ARFIT)
4
D1
Digital input 1 (Connect to terminal 2 of the ARFIT flow regulator to enable operation)
5
E1
Analogue input 1 (Control 0-10V) (Terminal 4 flow regulator ARFIT)
6
PE
Ground
7
11
Status relay, normally open,
Closes with alarm (2A, 250 VAC)
8
14
9
L1
Power - Phase
400 / 3 EN 1:50
(See characteristics on the motor plate)
10
L2
Power - Phase
11
L3/N
Power - Phase
Number Connection COR
Description
CON10
L
Black
Power - Phase
230 / 1 EN 1:50
(See characteristics on the motor plate)
CON11
N
Blue
Power - Neutral
CON12
PE
Green/Yellow
Ground
1
GND
Blue
GND – Connection for control interface (terminal 3 flow regulator ARFIT)
2
0-10V/PWM
Yellow
Control input 0 - 10V or PWM (Terminal 4 flow regulator ARFIT)
3
+10V
Red
Voltage output 10V (Terminal 5 flow regulator ARFIT)
4
TACH
White
Tachometer output Open collector, 1 pulse per rotation
Image 5