ArcTiv Technologies iPDU Скачать руководство пользователя страница 5

-  5  -

 

 

ARCTIV iPDU User Manual      M-0010--Rev 2

 

 
 

2. FUNCTIONS & START-UP 
 
2.1 

Functional Overview

 

 

Monitoring function

 

Through the local LCD screen, the user can view the following:

 

 

Current, voltage, energy consumption & power of each phase

 

 

Baud rate, serial communication address, daisy chain address, device 
series, IP address

 

 

Temperature & humidity status 

 

 

Current & power consumption of each individual outlet

 

 

Outlet switching function

 

Switching On/Off each individual outlet and circuit breaker, set up the power 
on/off delay, return to zero for power consumption at phase or outlet level.

 

 

Retain outlet status

 

Retain the former state of each outlet after restart.

 

 

User defined alarm

 

Triggered when thresholds of total current, individual outlet current or 
temperature & humidity are exceeded

 

 

System default alarm

 

When the total rating current, individual rating current are exceeded or 
temperature & humidity thresholds are exceeded.

 

 

Various alarm methods

 

Buzzer sounds, Alarm indicator flashes, value displayed in red from Web 
interface, flashing red LCD screen, alarm logs, E-mail notification and SNMP trap

 

 

User management

 

User permission configuration (User can be set as administrator or normal user).

 

 

Access methods

 

Web Interface, Telnet command line, Modbus, SNMP (v1, v2c, v3), Serial console

 

 

LCD screen energy-saving mode and mute alarm buzzer 

 

 

Multi-user operation system & browser and remote software update.

 

Содержание iPDU

Страница 1: ...Logo is a registered trademark of ArcTiv Technology Co Ltd Copyright 2021 ARCTIV Technologies LLC USA All rights reserved No part of this document may be reproduced in any way without the expressed w...

Страница 2: ...UNCTIONS START UP 5 2 1 Functional Overview 5 2 2 Product Pictures and Functional Diagram 6 3 HARDWARE INSTRUCTION 8 3 1 Network Module 8 3 2 System Initialization 8 3 3 Hardware Settings 9 3 4 Daisy...

Страница 3: ...and technical personnel Because the PDU output module base is charged ensure proper insulation and protection during the maintenance of the equipment Before disassembling the output module please remo...

Страница 4: ...et The standard features for each range include Feature Metered Input Metered Outlet Managed Monitoring of each phase Energy Power PF Voltage Current Steel Chassis Hot swap Network Module Hot swap Out...

Страница 5: ...Retain the former state of each outlet after restart User defined alarm Triggered when thresholds of total current individual outlet current or temperature humidity are exceeded System default alarm...

Страница 6: ...6 ARCTIV iPDU User Manual M 0010 Rev 2 2 2 Product Pictures and Functional Diagram Network Module Managed PDU 0U High Density Managed PDU 0U Outlet Module Managed PDU 1U...

Страница 7: ...TROL Confirm and flip button 9 RESET Reset button 10 NET 10 100M Ethernet port 11 SER Serial port MODBUS Supported 12 IN Daisy Chain port Connect to the OUT port of previous PDU 13 OUT Daisy Chain por...

Страница 8: ...and hold the control button then press RESET button to restore to factory settings UP Page Up Scroll up to the previous page DOWN Page Down Scroll down to the new page RESET RESET Button Restart syste...

Страница 9: ...t power consumption of each phase 3 3 Hardware Settings Restore to factory settings Press and hold the CONTROL button to power on the PDU at the same time Or press and hold the CONTROL button and pres...

Страница 10: ...the user can manage multiple PDUs from one IP address through the web interface Daisy chain schematic is as follows Ethernet Daisy Chain settings 1 Log in each PDU and configure the Work mode Master u...

Страница 11: ...Serial Server connects to the Bus arbiter the RS485 port from the Bus arbiter connects to the SER port from each PDU Serial connection can support up to 32 PDUs together See figure below 1 Log on to...

Страница 12: ...U OUT port to the IN port of the second PDU Connect all 32 Slave unit by the same way see Figure above Serial connection can support up to 32 PDUs together See figure as below 1 Log on to Web interfac...

Страница 13: ...ds Access through the Web Interface through the following Supports browsers IE Google chrome Firefox etc SNMP V1 V2c V3 Command line interface telnet Serial communication MODBUS RTU Web Interface Open...

Страница 14: ...below Input monitoring The input current voltage power energy power factor of each phase and On Off status of circuit breaker Outlet Monitoring The current power consumption and ON OFF status of each...

Страница 15: ...iPDU User Manual M 0010 Rev 2 Input Threshold Settings The input voltage threshold range 0 250VAC The input current threshold range 1P 0 63A 3P 0 32A Temperature Humidity threshold range 0 400 C temp...

Страница 16: ...2 Individual Outlet Threshold Settings The individual outlet current threshold range 0 16A User defined power On Off delay for individual outlets 0 10 seconds Note The low load and overload threshold...

Страница 17: ...rn To Zero User can view the power consumption of individual outlet or each phase The specified power consumption can be returned to zero by clicking the Reset button The power consumption value of sp...

Страница 18: ...ick the ON OFF button after the outlet to switch ON OFF the specified individual outlets Click the ON OFF button after each phase to switch ON OFF the outlets from the specified phase Click All ON All...

Страница 19: ...M 0010 Rev 2 Switch Group Tick off the box from the Outlet Groups listed Select Enable from the dropdown list and click Save button By clicking the ON or OFF button you can switch on off the outlets t...

Страница 20: ...list select the administrator or normal user account Next to the corresponding output bit name click the symbol to have the output bit control permission and the unsigned symbol is no output bit cont...

Страница 21: ...21 ARCTIV iPDU User Manual M 0010 Rev 2 Device Management Device Settings To configure the device name LCD screen energy saving mode mute the buzzer alarm Work mode Modbus address code and baud rate...

Страница 22: ...under normal work mode HTTPS SSL Mode Port is 443 by default Note These settings will take effect when PDU is restarted Network settings and modify IP address for example IP address 192 168 1 163 fac...

Страница 23: ...m the DHCP drop down list and click Save to enable it After restarting the software the device will receive the IP automatically IP can be viewed from the LCD screen Note When DHCP is On the device au...

Страница 24: ...read community and write community The default Read community and Write community is public and private respectively Trap address can set 2 trap addresses Fill in the trap address of SNMP management...

Страница 25: ...SMTP service including SMTP account password SMTP server working mode SMTP SMTPS and e mail recipients up to 5 recipients then Click Save SMTP settings will take effect when PDU is restarted SMTP test...

Страница 26: ...ngs Telnet Select Enable or Disable Enable by default and save make sure to restart the software after modification Telnet account and password is the same one used for login Telnet port is 23 Note te...

Страница 27: ...gs Local time calibration Click Time Acquisition to synchronize the iPDU system time to the local machine Network time calibration Click Time Acquisition to synchronize the iPDU system time and date t...

Страница 28: ...ount Select the user account from the user list and click Delete Note The maximum length for user name and passwords is 10 characters the user name and password exceeds the maximum of 10 characters wi...

Страница 29: ...e of the log Every page display 30 logs and maximum support to 10 pages the initial pages will be deleted when over 10 pages To delete the log click Delete on the web page at the prompt check OK to de...

Страница 30: ...estore to factory settings from the system command drop down list SNMP access This software supports SNMP V1 V2C and V3 a MIB file can be provided at customer s request User can view the power informa...

Страница 31: ...ly Telnet does not support the Daisy chain connection user can only access and manage the Master unit To open the Telnet client by Start Run command enter Telnet in the input box and click OK Enter th...

Страница 32: ...ata including current voltage power power factor and power consumption on each phase Command line format PHASE as shown below OUTPUT Command Use the OUTPUT command to view the current power power cons...

Страница 33: ...old Command line format SENSOR see figure below ON OFF Command Use the ON OFF command to switch On Off the individual outlet outlets from each phase or all outlets Command line format ON OFF index ope...

Страница 34: ...h Off the outlet 1 OUTPUT command can switch ON OFF one outlet at one time GROUP Enter command line on group 1 to switch on outlet from branch circuit 1 Enter command line off group 1 to switch off ou...

Страница 35: ...nd to logout the Telnet command line as shown below HELP Command Use the HELP command to shows general help as shown below MODBUS RTU access Use two wire RS 485 serial communication port for serial ac...

Страница 36: ...8 24 36 42 Outlets Output Voltage 1P 100VAC 240VAC 50 60 Hz Max Output Current 16A 32A Max Phase Current 16A 32A Control Ports NET Port 1xRJ45 Ports Daisy Chain Port 2xRJ45 Ports SER Port 1xRJ45 Ports...

Страница 37: ...ng 0U Tool less button 1U EIA Rails Case Color Black Accessories included Installation Bracket 1 Set Network Cable 2M Blue Serial Cable 2M White User Manual 1 set CD Optional Sensor Temperature Humidi...

Страница 38: ...arranty Problems caused because of improper maintenance Problems caused because of unauthorized change modification or improper use The devices are not used in the rated physical environment Problems...

Отзывы: