- 36 -
ARCTIV iPDU User Manual M-0010--Rev 2
5. TECHNICAL SPECIFICATIONS
Items
Specifications
Voltage
Input Voltage
1P: 100VAC
–
240VAC (50/60 Hz)
3P: 200VAC
–
400VAC (50/60 Hz)
Input Plug
Standard IEC Plug or connector
Power Cord
32A: 3x6mm
2
63A: 3x16mm
2
3*16A: 5x2.6mm
2
3*32A: 5x6.0mm
2
Cable Length
3M
Max Load Current
1P: 16A, 32A, 63A,
3P: 3x16A, 3x32A
Overload Protection 16A / 32A hydraulic breaker
Output
Sockets
IEC320 C13 (locking), C19
Socket Quantity
8 / 24 / 36 / 42 Outlets
Output Voltage
1P: 100VAC
–
240VAC (50/60 Hz)
Max Output Current 16A, 32A
Max Phase Current
16A, 32A
Control
Ports
NET Port
1xRJ45 Ports
Daisy Chain Port
2xRJ45 Ports
SER Port
1xRJ45 Ports
Temp & Humid Port 2xRJ11 Ports
Audible and Visual
Alarm Port
1xRJ11 Ports
Display
Working State
1xLED
Power Pulse
1xLED
Alarm
1xLED
IP Address, PDU
State, Value, Alarm
2.
8”
LCD Screen
Load
Current
Display
Total Current
16A / 32A, (1% accuracy)
Resolution: 0.01A, Response: 500ms
Individual Load
Current
10A / 16A, (1% accuracy)
Resolution: 0.01A, Response: 500ms
Sensors
Temperature
0
0
C ~ +45
0
C (+/- 1
0
C)
Response: 400ms
Humidity
10 ~ 90%, (5% accuracy)
Response: 400ms