Table. 5.3.6 - 83. Operating time characteristics setting parameters.
Name
Range
Step
Default
Description
FWD
reset
time
0.000…1800.000s 0.005s 0.300s
Forward start detection reset time. Starts to count from the first detected
forward (faulty feeder) spike. If while counting another spike is detected,
it resets and starts from the beginning. If it runs to the end, it resets the
function's STARTFWD signal.
REV
reset
time
0.000…1800.000s 0.005s 0.300s
Reverse start detection reset time. Starts to count from the first detected
reverse (healthy feeder) spike. If while counting another spike is
detected, it resets and starts from the beginning. If it runs to the end, it
resets the function's STARTREV signal.
Definite
operating
time
delay
0.000…1800.000s 0.005s 0.500s
Operating time counter that starts from the beginning of the fault if the
FWD reset time is running and the function has a START signal on. If the
FWD reset time is reached and the function releases, this timer is reset
as well.
Spikes to
trip >
1...50
1
2
The calculated cumulative spikes comparator. In order for the function
to trip, a set number of spikes must be exceeded. If the set operating
time is reached but the calculated spike number is below this, the setting
function releases without a trip when the FWD reset time has elapsed.
Events and registers
The intermittent earth fault function (abbreviated "IEF" in event block names) generates events and
registers from the status changes in the detected earth fault, in the FWD start, in the REV start, in TRIP,
and in BLOCKED. The user can select which event messages are stored in the main event buffer: ON,
OFF, or both.
The events triggered by the function are recorded with a time stamp and with process data values.
Table. 5.3.6 - 84. Event codes.
Event number
Event channel
Event block name
Event code
Description
7296
114
IEF1
0
Start FWD ON
7297
114
IEF1
1
Start FWD OFF
7298
114
IEF1
2
Start REV ON
7299
114
IEF1
3
Start REV OFF
7300
114
IEF1
4
Trip ON
7301
114
IEF1
5
Trip OFF
7302
114
IEF1
6
Block ON
7303
114
IEF1
7
Block OFF
7304
114
IEF1
8
Intermittent EF detected ON
7305
114
IEF1
9
Intermittent EF detected OFF
7306
114
IEF1
10
Normal earthfault detected
7307
114
IEF1
11
Intermittent EF Locked
The function registers its operation into the last twelve (12) time-stamped registers. The register of the
function records the ON event process data for START, TRIP or BLOCKED. The table below
presents the structure of the function's register content.
A
AQ
Q-F215
-F215
Instruction manual
Version: 2.04
141
Содержание AQ-F215
Страница 1: ...AQ F215 Feeder protection IED Instruction manual ...
Страница 430: ...Figure 7 4 261 Example block scheme A AQ Q F215 F215 Instruction manual Version 2 04 429 ...
Страница 452: ...Figure 8 14 284 Panel cutout dimensions and device spacing A AQ Q F215 F215 Instruction manual Version 2 04 451 ...
Страница 487: ...10 Ordering information A AQ Q F215 F215 Instruction manual Version 2 04 486 ...