GENERAL INFORMATION

 

This appliance is tested and certified to the following U.S. and Canadian gas appliance standards.

 

-

 ANSI Z 21.88b

-

2014 / CSA 2.33b

-

2014, Vented Gas Fireplace Heater

 

-

 CAN/CGA

-

2.17

-

M91, Gas

-

Fired Appliances for Use at High Altitudes.

 

Please contact Archgard Industries Ltd., if you have any questions regarding the certification of these 

appliances.

 

APPLIANCE CERTIFICATION

 

INSTALLATION CODES

 

This appliance must be installed by a qualified gas appliance installer. The installation must conform with the local 

codes or, in the absence of local codes, with the current National Fuel Gas Code, ANSI Z223.1/ NFPA 54, in the 

US or Installation Code, CAN/CGA

-

B149, in Canada. Electrical connections and grounding must conform with 

local code, or current National Electrical code, ANSI/NFPA No. 54, in the U.S. and in Canada, the current 

Canadian Electrical Code, CSA C22.1. This appliance is certified for installation in a bedroom or a bedsitting room 

and conforms to CR89

-

001.

 

We recommend that our gas hearth products be installed and serviced by professionals who are 

certified in the U.S. by the National Fireplace Institute® (NFI) as NFI Gas Specialists.

 

HIGH ALTITUDE INSTALLATION 

 

When installing this appliance beyond 4500 ft. (1372 m) above sea level, the appliance must be properly de

-

rated 

and installed according to local codes, in the absence of local codes, with the current National Fuel Gas Code, 

ANSI Z223.1/ NFPA 54, in the U.S. or Installation Code, CAN/CGA

-

B149, in Canada.

 

 

Natural Gas (NG)

 

Propane (LP)

 

Manifold Pressure

 

1.6 

-

 3.5 in. w.c. (0.4 

-

 0.9 kPa)

 

6.3 

-

 10.0 in. w.c. (1.6 

-

 2.5 kPa)

 

Minimum Supply Pressure for 

Purpose of Input Adjustment 

 

5 in. w.c. (1.2 kPa)

 

11.0 in. w.c. (2.8 kPa)

 

Maximum Supply Pressure for 

Purpose of Input Adjustment 

 

14 in. w.c. (3.5 kPa)

 

14.0 in. w.c. (3.6 kPa)

 

Orifice Size

 

Cap #45 DMS (2.08 mm dia.)

 

Cap #55 DMS (1.32 mm dia.)

 

Nominal Input Rating

 

15,000 

-

 20,000 BTU/hr (4.4 

-

 5.8 kW) 

 

16,000 

-

20,000 BTU/hr (4.6 

-

 5.8 kW)

 

Altitude

 

-

 4,500 ft. (0 

-

 1372 m)

 

-

 4,500 ft. (0 

-

 1372 m)

 

Primary Air Opening

 

3/16 in. (5 mm)

 

Fully Open

 

SPECIFICATIONS

 

Содержание 25-BVI20N-3

Страница 1: ...and liquids in the vicinity of this or any other appliance WHAT TO DO IF YOU SMELL GAS Do not try to light any appliance Do not touch any electrical switch do not use any phone in your building Leave...

Страница 2: ...or of the side wall horizontally vented gas fueled equipment shall not approve the instal lation unless upon inspection the inspector observes carbon monoxide detectors and signage installed in accord...

Страница 3: ...thetics and heat output can be adjusted to suit the owner s moods and heating needs Solid Construction Constructed mainly of 16 and 18 gauge satin coated steel for long life and durability Please read...

Страница 4: ...ns 8 Log Placement 15 Operation Instructions 20 Maintenance 22 Troubleshooting Instructions 23 Servicing 25 APPENDIX A Installation Into Vented Gas Fireplaces 28 Suitable Host Fireplaces Specific Inst...

Страница 5: ...compartments burners and circulating air passageways for the appliance be kept clean Trim panels or surrounds shall not seal ventilation openings in the fireplace CAUTION FOR YOUR SAFETY Do not insta...

Страница 6: ...nstallation in a bedroom or a bedsitting room and conforms to CR89 001 We recommend that our gas hearth products be installed and serviced by professionals who are certified in the U S by the National...

Страница 7: ...S BAY GLASS DOOR REMOVABLE CONTROL COVER SURROUND FRONT VIEW SPARKER APPLIANCE DIMENSIONS A B I K J A 30 768 mm B 23 584 mm C 15 387 mm D 11 286 mm E 4 102 mm F 19 489 mm G 5 127 mm H 5 146 mm I 24 61...

Страница 8: ...y factory built wood burning and specific zero clearance vented gas fireplaces Due to constant additions contact Archgard Industries for an updated list of suitable gas fireplaces This appliance canno...

Страница 9: ...esult in property damage or personal injury The installer must mechanically attach the following warning included in the manual bag to the inside of the fire box of the fireplace into which the gas fi...

Страница 10: ...ust not be removed or altered side and top of door frame side and top of the face of fireplace metal sides etc If the factory built fireplace has no gas access hole s provided an access hole of 1 1 2...

Страница 11: ...ng and possible death This appliance must not be connected to a chimney flue serving a separate solid fuel burning appliance The appliance may be vented using 4 in diameter aluminum or stainless steel...

Страница 12: ...flat tip screw driver and placing a test gauge on the tap The minimum permissible gas supply pressure is 4 5 in w c 1 2 kPa for natural gas and 11 0 in w c 2 8 kPa for propane Maximum gas supply press...

Страница 13: ...es on the bracket that best suit your application INSTALLATION INSTRUCTIONS Continued 1 2 3 The spill switch is manual reset type that can be reset by pressing the pin between the two wire terminals w...

Страница 14: ...bottom of the door towards you Lift up the door to unhook it from the body Place the door at a safe location where it cannot be scratched or damaged Replacing the Glass Door Installation of the glass...

Страница 15: ...an the amount and type supplied with the unit LOG PLACEMENT WARNING Do not place the logs or branches in any configuration other than the one shown A fire explosion or excessive carbon monoxide CO may...

Страница 16: ...rt using locator pins and pre drilled holes in log Log will sit as shown in the photo below STEP 2 Locate log 2 and place onto the left side of the burner using locator pins and pre drilled holes in l...

Страница 17: ...er using the locator pins and pre drilled holes in log Log should sit as shown in photo below STEP 4 Locate log 4 and place onto right side of burner using the locator pins and pre drilled holes in lo...

Страница 18: ...he locator pins and pre drilled holes in log Log should sit as shown in photo below STEP 6 Locate log 6 and place onto rear log using the locator pins and pre drilled holes in log Log should sit behin...

Страница 19: ...place onto rear log using the locator pins and pre drilled holes in log Log should sit behind left grate tine as shown in photo below FINAL LOG PLACEMENT Please note that all logs should be placed ex...

Страница 20: ...lt in a fire or explosion BEFORE LIGHTING smell all around the appliance area for gas Be sure to smell next to the floor because some gases are heavier than air and will settle on the floor IF YOU SME...

Страница 21: ...ing of pilot Press slightly and turn control knob counterclockwise to PILOT position depress control knob and light pilot by repeatedly pressing the sparker Venting of air may take place at the pilot...

Страница 22: ...gular services listed above Inspect and operate the pressure relief mechanism door buckles to verify they are free from ob struction and operate properly Carefully remove the logs and gently brush off...

Страница 23: ...ay be blocked or the gas valve may be defective 5 Check wiring and connections to spill switch Pilot will not remain on after being lit 1 Press the control knob all the way in 2 Hold the control knob...

Страница 24: ...for correct ohms reading Replace if required 7 Check for proper drafting of the appliance Correct if drafting is occurring into the room 8 Spill switch has tripped Reset by hand when appliance has coo...

Страница 25: ...CING UNDER WARRANTY Remove the control cover The pressure test taps are located on the front of the valve The supply pressure is marked IN and the manifold pressure is marked OUT There is also an arro...

Страница 26: ...now visible Use a 11 32 hex socket and remove the three nuts holding the fan to the back of the firebox Disconnect the spade connectors to the fan Carefully remove the fan Reverse the above instructio...

Страница 27: ...r tray by loosening and removing the two mounting screws located next to the two back log locating tabs Shut of the gas to the appliance and disconnect the gas line to the appliance If the appliance h...

Страница 28: ...n updated list of gas fireplaces and any additional installation instructions The host gas fireplace s certification will be nullified and will no longer be usable for its original purpose A warning p...

Страница 29: ...ox Remove or trim any baffles inside the firebox that may be obstructing the direct passage to the flue connector Remove or trim any decorative facing or baffles inside the firebox that may interfere...

Страница 30: ...O 25 as it is being inserted into the host fireplace Level the EURO 25 as described in manual Complete the installation of the surround and accessories as described in the manual Check for proper vent...

Страница 31: ...personal injury or loss of life SAMPLE MODIFICATION WARNING PLATE 303 0050 WARNING This fireplace has been modified for use with the Archgard EURO 25 gas insert Usage without the EURO 25 gas insert m...

Страница 32: ...on of the host gas fireplace is complete See Appendix A of the Euro 25 manual for further instructions All installation requirements in the manual must also be carefully observed and followed 7 Use Ar...

Страница 33: ...of the Euro 25 manual for further instructions All installation requirements in the manual must also be carefully observed and followed 6 Use Archgard 25 ICKIT5 connector kit to connect the insert to...

Страница 34: ...also be carefully observed and followed 8 Use Archgard 25 ICKIT5 connector kit to connect the insert to the host s B vent or connect a 4 diameter flexible aluminum gas vent from the insert to the hos...

Страница 35: ...is complete See Appendix A of the Euro 25 manual for further instructions All installation requirements in the manual must also be carefully observed and followed 8 Use Archgard 25 ICKIT5 connector k...

Страница 36: ...chgard 25 ICKIT5 connector kit to connect the insert to the host s B vent or connect a 4 diameter flexible aluminum gas vent from the insert to the host s vent cap Optional custom surround is availabl...

Страница 37: ...NAME ADDRESS PHONE NUMBER COMPANY NAME ADDRESS PHONE NUMBER APPLIANCE MODEL NUMBER 25 BVI20N 3 SERIAL NUMBER GAS TYPE NATURAL GAS LPG VALVE TYPE Robertshaw 7000MVRB DATE PURCHASED INSTALLATION INSTAL...

Страница 38: ...ve When calling for help please have the following information Model of your Fireplace Serial Number Place of Purchase Date of Purchase Problem Description NOTE Warranty may be void if work is carried...

Страница 39: ...0044 SPILL SWITCH 350 F MANUAL RESET 1 EA 305 0027 SWITCH BLANK ON OFF CARLING 9711 1 EA 308 0005 PIEZO IGNITOR c w NUT JBS 66270 003 1 EA 308 0043 VALVE 7000MVRB 5LC NG c w KNOB 1 EA 308 0093 PILOT A...

Страница 40: ...25 BVI20N 3 40 NOTES...

Страница 41: ...ler s Name Address City State Prov ZIP Phone _____ Installer s Name Address City State Prov ZIP Phone _____ Why did you choose this product Thank you for purchasing our product and filling out this wa...

Страница 42: ......

Страница 43: ...25 BVI20N 3 43 NOTES...

Страница 44: ...Archgard Industries Ltd 7116 Beatty Drive Mission B C V2V 6B4 Canada Website www archgard com...

Отзывы: