 On-site requirements 

6.

 

It is necessary to check on-site circumstances such as the bearing capacity of the floor before the 

installation. Depending on the model, the total weight of the fireplace insert (including cladding) may 

be up to 600 kg. 

 

If it is not possible to evaluate the bearing capacity of the floor (wooden beam ceilings, for 

instance), then a structural engineer should be consulted. Flammable floor coverings must be 

protected by a covering of non-flammable materials in front of the opening to the 

combustion chamber. 

The covering should extend at least 50 cm to the front and at least 30 cm to each side, 

measured from the opening to the combustion chamber or inspection glass. 

 

See Chapter 13 for the distances to the rear and sides between the Vita System and any materials 

which are flammable or require protection. Fire safety. You can find information on the chimney 
configuration in the installation instructions of the fireplace insert in question

.

 

 

 Storage medium material

 

7.

 

Vita Systems are made up of a heat-resistance storage medium and exhibit the typical characteristics 

of concrete in terms of surface and appearance. In spite of great care taken during production and 

transport, slight irregularities, small cracks or rough edges cannot be completely eliminated and are 

no reason to file a complaint. All storage elements are produced in accordance with the 

requirements of exposed storage class SB2 and are inspected prior to delivery by in-house quality 

assurance to ensure they are in good condition. 

 

 Surface 

8.

 

 

Repair of minor damage 

The Vita System comes with a repair set of storage medium for rectifying minor damage such as 

chips or hairline cracks. To use properly, stir  the storage medium with water until a dense 

consistency has been reached. Before applying it with a spatula, dampen the surfaces to be worked 

on so that the materials can achieve a permanent connection.   

 

 

 

Surface design 

The surfaces of Vita Systems can be refined with commercially available silicate paints or plaster 

materials, as desired. Make sure to select a wall covering which is able to continuously withstand 

temperatures of over 150°C. 

The system should only be coated 24 hours after assembly to make sure that all of the glue 

connections have hardened. If any surfaces were spackled over beforehand, they must be smoothed 

out with fine sandpaper.   

 

 

 

 

 

 

Содержание Vita System angolo 39/58

Страница 1: ...mi Stra e 11 39100 Bolzano Bozen BZ Installation instructions Vita Systeme Vita System angolo 39 58 Vita System angolo 58 39 Vita System angolo 45 45 Vita System frontale 45 Vita System frontale 60 Vi...

Страница 2: ...on air side connection 6 10 Flue side connection 8 11 Flue and combustion air connection dimension sheet 8 12 Fire protection 14 12 1 Floor coverings near the fireplace 14 12 2 Radiation protection 15...

Страница 3: ...errors Symbol key 2 A variety of symbols are used in these instructions Observance of these symbols is of central importance to ensure the correct planning installation and operation of this product F...

Страница 4: ...s expedient that you attach a protective fixture for these groups of persons as the view pane and the cladding parts of the fireplace can become extremely hot Risk of burning Never leave these groups...

Страница 5: ...l characteristics of concrete in terms of surface and appearance In spite of great care taken during production and transport slight irregularities small cracks or rough edges cannot be completely eli...

Страница 6: ...ll be necessary to make a cut out in an element of the system For this purpose there is a recess in the right position on the inside of the cladding element which must be opened beforehand Proceed as...

Страница 7: ...the sawing smooth the edges and then clean up the surface with non woven abrasive if necessary It is a good idea to protect the cut out contour with tape in order to prevent the edges from breaking of...

Страница 8: ...llation process In this case disassemble the elbow and put it aside for subsequent installation The storage elements must be cut out to enable a rear flue gas connection To make the cut out proceed as...

Страница 9: ...9 Vita System frontale 45 SX DX Vita System frontale 45 SL...

Страница 10: ...10 Vita System frontale 60 SX DX Vita System frontale 60 SL...

Страница 11: ...11 Vita System frontale 80 SL...

Страница 12: ...12 Vita System angolo 45 45 SX DX Vita System angolo 45 45 SL...

Страница 13: ...13 Vita System angolo 39 58 DX SL Vita System angolo 58 39 SX SL...

Страница 14: ...ble materials The covering must extend from the combustion opening by at least 50 cm to the front and at least 30 cm to the sides The non flammable covering may be made of ceramic such as tiles or fla...

Страница 15: ...s prevents thermal stress points from forming and adjoining components becoming heated to an impermissible degree Radiation protection sheets for wall connections are available as an accessory As an a...

Страница 16: ...16 Free standing installation mode Vita System angolo 45 45 58 39 39 58 5cm 50cm 15cm...

Страница 17: ...17 12 4 Distances to flammable installation walls Wall flush installation mode for Vita System frontale 45 60 80 Only permissible when a radiation protection sheet is used 50cm 15cm...

Страница 18: ...18 Wall flush installation mode for Vita System angolo 45 45 58 39 39 58 Only permissible when a radiation protection sheet is used 50cm...

Страница 19: ...process on the Vita System frontale 60 SL model but the same process can be used on the other models Separate instructions are provided for device specific exceptions on other models Inspect the syst...

Страница 20: ...element must be completely pushed up against the installation wall Special instructions on the Classic corner decoration elements in the case of wall flush installation If the Classic corner decorati...

Страница 21: ...by at least 2 persons Now align the fireplace insert at the front and adjust it to the suitable height Observe the dimensions specified in the white boxes below Connecting the combustion air duct Onc...

Страница 22: ...1 is installed The connection of the individual system modules to each other can be reinforced with mortar or heat resistant silicon adhesive In the case of the cladding version equipped with a heart...

Страница 23: ...ounts provided for fastening the screen must be screwed onto the fireplace insert after cladding elements 1 2 have been installed To accomplish this attach the angled steel profiles to the body as sho...

Страница 24: ...ended for it In this case the hearth must be positioned beneath the sill of the fireplace insert In doing so pay attention to the horizontal and vertical fitting and reinforce the seams with adhesives...

Страница 25: ...ase of a rear connection the upper cladding element must be cut out for the flue pipe To do this follow the instructions for the flue side connection in these instructions The connection of the indivi...

Страница 26: ...Vita System delivery and must be ordered separately Installing the radiation protection sheets There are retainers for fastening included with each radiation protection sheets These must be attached t...

Страница 27: ...ust be loosened and the removed upward Adjust the connection line in length a the necessary length varies depending on the distance from the wall and completely press it into the wall lining of the ch...

Страница 28: ...ection direction the connection pipe may only be inserted after the top plate has been put in place Installing the corner elements The Vita Systems corner elements may be attached using conventional m...

Страница 29: ...r frame onto the fireplace insert and readjust the combustion chamber frame if necessary Storage elements 2 5 must end parallel to the screen To do so insert the combustion chamber frame straight into...

Страница 30: ...st be placed onto the system When doing so make sure that it fits flush to the cladding elements The dummy cover for the flue gas connection on top must be removed before the top plate is placed on an...

Страница 31: ...ying the plaster to the surface Dampen the surfaces with a sponge so that the bonding finish to be applied can take a good hold on the stone surface The processing temperature must be 10 C To prevent...

Отзывы: