33
26) The top display shows the parameter being
tested, BOIL. BOIL is the storage cylinder pump
(PB).
27) Press MENU (the top display shows OFF flashing).
28) Use buttons 3 and 4 to set the value to ON and check the storage cylinder pump (PB) output at terminals
10 – 11 - 12 on the terminal block.
29) Press ESC.
30) Press button 3.
31) The top display shows the parameter being
tested, SOLA. SOLA is the solar panel pump (PS).
32) Press MENU (the top display shows OFF flashing).
33) Use buttons 3 and 4 to set the value to ON and check the solar panel pump (PS) output at terminals 13 –
14 - 15 on the terminal block.
34) Press ESC.
35) Press button 3.
36) The top display shows the parameter being
tested, VALV. VALV is the selector valve (VD).
37) Press MENU (the top display shows OFF flashing).
38) Use buttons 3 and 4 to set the value to ON and check the selector valve (VD) output at terminals 23 – 24 -
25 on the terminal block.
* Parameter VALV should only be tested if its function is featured, i.e. on ASPIRO – REGOVENT COMBI
boilers.
39) Press ESC.
40) Press button 3.
41) The top display shows the parameter being
tested, BRUC. BRUC is the gas / oil burner in combi
boilers.
41) Press MENU (the top display shows OFF flashing).
42) Use buttons 3 and 4 to set the value to ON and check the gas / oil burner output at terminals 20 – 21 - 22
on the terminal block.
* Parameter BRUC should only be tested if its function is featured, i.e. on ASPIRO – REGOVENT COMBI
boilers.
43) Press ESC.