32
AQ-OP-00010_E
B.3.3 SMA Sunny Island
221.02
BatCpyNom .................................................. 612 Ah
221.03
BatVtgNom ...................................................... 48 V
222.01
BatChrgCurMax ................................ 144 A/Module
222.02
AptTmBoost ................................................. 60 min
222.03
AptTmFul .......................................................... 1 hr
222.04
AptTmEqu ......................................................... 1 hr
222.05
CycTmFul ................................................... 180 days
222.06
CyCTmEqu ................................................. 180 days
222.07
ChrgVtgBoost .............................................. 2.45 V*
222.08
ChrgVtgFul .................................................. 2.45 V*
222.09
ChrgVtgEqu ................................................. 2.45 V*
222.10
ChrgVtgFlo .................................................... 2.20 V
222.11
BatTmpCps ............................................... 10 mV/°C
223.05
BatPro1Soc........................................................ 25%
223.06
BatPro2Soc........................................................ 30%
223.07
BatPro3Soc........................................................ 25%
224.01
SilentEna ...................................................... enable
224.02
SilentTmFlo ....................................................... 1 hr
224.03
SilentTmMax ................................................... 48 hr
Parameter nubmers are for model Sixx48-US. Parameters 224.01–224.03 not applicable to non-U.S. models.
* At 60 A charge rate; otherwise, refer to Section B.3.5.
B.3.4 Schneider Conext XW+
Batt Type ..................................................................... custom
Batt Capacity .................................................. 612 Ah/Module
Max Charge Rate .............................................. 144 A/Module
Charge Cycle ................................................................. 2 stage
ReCharge Volts ................................................................. 52 V
Absorb Time ................................................................... 1 min
Bulk Voltage ................................................................ 59.4 V*
Absorption Voltage ....................................................... 59.4 V
Equalize ........................................................................ disable
Batt Temp Comp ........................................................... -0.180
Grid Supp Volts ............................................................. 52.8 V
* At 60 A charge rate; otherwise, refer to Section B.3.5.