15
AQ-OP-00010_E
Charging the battery to 100% SOC daily or periodically is not required to maintain battery life.
The AHI battery chemistry can be maintained at a partial or low state of charge indefinitely.
The Module can be discharged within its operating limits as well, as defined in Product Specification
Sheet, available on the Aquion Energy Customer Portal at
http://info.aquionenergy.com/customer-
portal
.
The AHI battery is designed for long duration charge and discharge. The battery’s high impedance
causes its voltage response to high current levels to be higher than lead acid or lithium ion battery
solutions of equivalent capacity. The supplemental charger settings (i.e., generator- or grid-tie) may
need to be adjusted so that at low battery state of charge, high inrush loads will not trigger a low
battery fault condition in the power electronics.
6.4 State of Charge