B.2.5 Schneider Conext XW+
Batt Type ..................................................................... custom
Batt Capacity .................................................. 612 Ah/Module
Max Charge Rate .............................................. 144 A/Module
Charge Cycle ................................................................. 3 stage
Float Voltage ................................................................. 54.4 V
Absorb Time ................................................................... 1 min
Bulk Voltage ................................................................ 59.4 V*
Absorption Voltage ..................................................... 59.4 V*
Equalize ........................................................................ Disable
Batt Temp Comp ........................................................... -0.180
* At 60 A charge rate; otherwise, refer to Section B.3.5.
B.3 Grid-Tied/UPS Device-Specific Settings by Manufacturer
Different settings apply if the battery is to be used primarily in a grid-tied, UPS-type application. The goal
of off-grid, solar/battery charged applications is to charge the battery as fast as possible when power is
available. The grid-tied or UPS use case emphasizes providing voltage settings that ensure the long-term
life of the battery and maximum available energy when required. To achieve this goal, the battery will
use a lower float voltage or utilize silent mode settings.
B.3.1 MidNite Classic
T-Comp ................................................................................................................................................... -8 mV
Equalization ................................ equalization is not needed; verify that CHARGE>EQ>AUTOEQ>AUTO = 0
Current Limit – CHARGE>LIMITS>Out Amps ............................................................................ 144 A/Module
Absorb Voltage – CHARGE> VOLTS>Absorb Volts .............................................................................. 59.4 V*
Equalize Voltage – CHARGE> VOLTS>Equalize Volts ............................................................................. 52.8 V
Float Voltage – CHARGE> VOLTS>Float Volts ....................................................................................... 52.8 V
Absorb Time ......................................................................................................................................... 60 min
* At 60 A charge rate; otherwise, refer to Section B.3.5.
B.3.2 Outback
Charge Controller Menu
Absorb Voltage ............................................................ 59.4 V*
Absorb Time ...................................................................... 1 hr
Float Voltage ................................................................. 52.8 V
ReBulk Voltage ................................................................. 50 V
Output Current Limit ........................................ 144 A/Module
Absorb End Amps ............................................... 24 A/Module
* At 60 A charge rate; otherwise, refer to Section B.3.5.