background image

Filter is only to be used  

with cold water. 

Filter usage must comply  

with all state and local laws.

Testing was performed under standard laboratory 

conditions, actual performance may vary. 

Systems certified for cyst reduction may be used 

on disinfected waters that may contain filterable 

cysts. 

See owner’s manual for general installation 

conditions and needs plus manufacturer’s limited 

warranty.

• All contaminants reduced by this filter are listed. 

• Not all contaminants listed may be present in 

your water. 

• Filter does not remove all contaminants that may 

be present in tap water.

•  

Efficiency rating 

means the percentage of the influent 

water to the system that is available to the user 
as reverse osmosis treated water under operating 
conditions that approximate typical daily usage.

• 

 Recovery rating 

means the percentage of the influent 

water to the membrane portion of the system that is 
available to the user as reverse osmosis treated water 
when the system is operated without a storage tank or 
when the storage tank is bypassed.

This system has been tested for the treatment of water containing pentavalent arsenic (also known as As(V), 
As(+5), or arsenate) at concentrations of 0.30 mg/L or less. This system reduces pentavalent arsenic, but may not 
remove other forms of arsenic. This system is to be used on water supplies containing a detectable free chlorine 
residual at the system inlet or on water supplies that have been demonstrated to contain only pentavalent 
arsenic. Treatment with chloramine (combined chlorine) is not sucient to ensure complete conversion of 
trivalent arsenic to pentavalent arsenic. Please see the 

Arsenic Facts

 section of this Performance Data Sheet for 

further information.

Arsenic Facts

Arsenic (abbreviated As) is 
found naturally in some well 
water. Arsenic in water has no 
color, taste, or odor. It must be 
measured by a laboratory test.

Public water utilities must have 
their water tested for arsenic. 
You can get the results from 
your water utility. If you have 
your own well, you can have 
the water tested. The local 
health department or the state 
environmental health agency 
can provide a list of certified 
labs. The cost is typically $15 to 
$30. Information about arsenic 
in water can be found on the 
Internet at the U.S. Environmental 
Protection Agency website: 

epa.

gov/safewater/arsenic.html

.

There are two forms of arsenic: 

pentavalent arsenic

 As(V), As(+5), 

and arsenate) and 

trivalent arsenic 

(also called As(III), As(+3), and 
arsenite). In well water, arsenic 
may be pentavalent, trivalent, or 

a combination of both. Special 
sampling procedures are needed 
for a lab to determine what type 
and how much of each type of 
arsenic is in the water. Check with 
the labs in your area to see if they 
can provide this type of service. 
Reverse osmosis (RO) water 
treatment systems do not remove 
trivalent arsenic from water 
very well. RO systems are very 
eective at removing pentavalent 
arsenic. A free chlorine residual 
will rapidly convert trivalent 
arsenic to pentavalent arsenic. 
Other water treatment chemicals 
such as ozone and potassium 
permanganate will also change 
trivalent arsenic to pentavalent 
arsenic. A combined chlorine 
residual (also called chloramine) 
may not convert all the trivalent 
arsenic. If you get your water 
from a public water utility, contact 
the utility to find out if free 
chlorine or combined chlorine 
is used in the water system. The 

AQ-RO-3 system is designed to 
remove pentavalent arsenic. It will 
not convert trivalent arsenic to 
pentavalent arsenic. The system 
was tested in a lab. Under testing 
conditions, the system reduced 
[0.30 mg/L (ppm) or 0.050 mg/L 
(ppm)] pentavalent arsenic to 
0.010 mg/L (ppm) (the USEPA 
standard for drinking water) or 
less. The performance of the 
system may be dierent at your 
installation.

Have the treated water tested 
for arsenic to check whether 
the system is working properly. 
The RO component of the AQ-
RO-3 system must be replaced 
every 1-3 years to ensure that 
the system will continue to 
remove pentavalent arsenic. The 
component identification and 
locations where you can purchase 
the component are listed in the 
installation/operation manual.

Organic chemicals included by surrogate testing

VOCs  
(by surrogate testing using 
chloroform)

Drinking water 
regulatory level 
(MCL/MAC) mg/L

Influent/
Unfiltered

Effluent/
Filtered

Percent 
Reduction

alachlor

0.002

0.050

0.001

>98%

atrazine

0.003

0.100 

0.003

>97%

benzene

0.005

0.081 

0.001

>99%

carbofuran

0.04

0.190 

0.001

>99%

carbon tetrachloride

0.005

0.078

0.0018

98%

chlorobenzene

0.1

0.077 

0.001

>99%

chloropicrin

0.015

0.0002

99%

2,4-D

0.07

0.110

0.0017

98%

dibromochloropropane 

(DBCP) 

0.0002

0.052 

0.00002

>99%

o-dichlorobenzene

0.6

0.080 

0.001

>99%

p-dichlorobenzene

0.075

0.040 

0.001

>98%

1,2-dichloroethane

0.005

0.088

0.0048

95%

1,1-dichloroethylene

0.007

0.083 

0.001

>99%

cis-1,2-dichloroethylene

0.07

0.170 

0.0005

>99%

trans-1,2-dichloroethylene

0.1

0.086 

0.001

>99%

1,2-dichloropropane

0.005

0.080 

 0.001

>99%

cis-1,3-dichloropropylene

— 

0.079 

0.001

>99%

dinoseb

0.007

0.170

0.0002

99%

endrin

0.002

0.053

0.00059

99%

ethylbenzene

0.7

0.088 

0.001

>99%

ethylene dibromide (EDB) 

0.00005

0.044 

0.00002

>99%

haloacetonitriles (HAN)
Bromochloroacetontrile

0.022

0.0005

98%

Dibromoacetontrile

0.024

0.0006

98%

Dichloroacetontrile

0.0096

0.0002

98%

Trichloroacetontrile

0.015

0.0003

98%

haloketones (HK)
1,1-dichloro-2-propanone

0.0072

0.0001

99%

1,1,1-trichloro-2-propanone

0.0082

0.0003

 96%

heptachlor (H-34, Heptox)

0.0004

0.025 

0.00001

>99%

heptachlor epoxide

0.0002

0.0107

0.0002

98%

hexachlorobutadiene

0.044 

0.001

>98%

hexachlorocyclopentadiene 0.05

0.060 

0.000002 >99%

lindane

0.0002

0.055 

0.00001

>99%

methoxychlor

0.04

0.050 

0.0001

>99%

pentachlorophenol

0.001

0.096 

0.001

>99%

simazine

0.004

0.120 

0.004

>97%

styrene 

0.1

0.150 

0.0005

>99%

1,1,2,2-tetrachloroethane 

0.081 

0.001

>99%

tetrachloroethylene

0.005

0.081 

0.001

>99%

toluene

1

0.078 

0.001

>99%

2,4,5-TP (silvex) 

0.05

0.270

0.0016

99%

tribromoacetic acid

0.042 

0.001

>98%

1,2,4-trichlorobenzene

0.07

0.160 

0.0005

>99%

1,1,1-trichloroethane

0.2

0.084

0.0046

95%

1,1,2-trichloroethane

0.005

0.150 

0.0005

>99%

trichloroethylene

0.005

0.180 

0.0010

>99%

Trihalomethanes (THMs)

Influent/

Unfiltered

Effluent/

Filtered

Percent 

Reduction

Bromodichloromethane 

(THM)

0.080

0.300

0.015

95%

Bromoform (THM)
Chloroform (THM)
Chlorodibromomethane 

(THM)
Xylenes (total)

10

0.070 

0.001

>99%

Testing Performed under NSF/ANSI Standards 42 and 53 and in accordance with the California Department of Health Services Drinking Water Treatment Device Program. 
This system has been tested according to NSF/ANSI 42, 53, 58, 401 & P473 for reduction of the substances listed below. The concentration of the indicated substances in water 
entering the system was reduced to a concentration less than or equal to the permissible limit for water leaving the system, as specified in NSF/ANSI 42, 53, 58, 401 & P473. 

Do not use with water that is microbiologically  
unsafe or of unknown water quality without adequate 
disinfection before or after the system.

NSF/ANSI 42

Minimum 
reduction

Overall % 
reduction

Results

Chlorine Reduction, Free Available

<0.5 mg/l

97.66%

Pass

Chloramine Reduction, Free Available

<0.5 mg/l

97.66%

Pass

Particulate Reduction

85%

99.9%

Pass

NSF/ANSI 53

Required 
reduction

Overall % 
reduction

Results

Cyst Live Cryptosporidium & Giardia

99.95%

>99.99%

Pass

Mercury Reduction pH 8.5

<2 ug/L

>95.8%

Pass

Mercury Reduction pH 6.5

<2 ug/L

>96.5%

Pass

Lead Reduction pH 6.5

<10 ug/L

>99.4%

Pass

Lead Reduction pH 8.5

<10 ug/L

>99.3%

Pass

MTBE Reduction 

<5 ug/L

86.6%

Pass

Turbidity

<0.5 NTU

99.1%

Pass

VOC Surrogate Test 

95%

99.4%

Pass

Asbestos Reduction 

99%

>99%

Pass

NSF/ANSI 58

Maximum 
Concentration 

Minimum 
Reduction 

Overall % 
Reduction

Results

Arsenic Pentavalent

0.30

mg

/

L

 ±10%

 

80.0%

97.6%

Pass

Barium

10.0

mg

/

L

 ±10%

 

80.0%

95.2%

Pass

Cadmium

0.30

mg

/

L

 ±10%

 

83.3%

95.3%

Pass

Chromium Hexavalent

0.30

mg

/

L

 ±10%

 

66.7%

97.0%

Pass

Chromium Trivalent

0.30

mg

/

L

 ±10%

 

66.7%

96.6%

Pass

Copper

0.30

mg

/

L

 ±10%

 

56.7%

96.6%

Pass

Fluoride

8.0

mg

/

L

 ±10%

 

81.2%

95.7%

Pass

Lead

0.15

mg

/

L

 ±10%

 

93.3%

96.6%

Pass

Nitrate/Nitrite

30.0

mg

/

L

 ±10%

 

66.70%

82.40%

Pass

Radium 226/228

25

pCi

/

L

 ±10%

 

80.0%

80.0%

Pass

Selenium

0.10

mg

/

L

 ±10%

 

50.0%

97.9%

Pass

TDS

750

mg

/

L

 ±10%

 

75.0%

95.0%

Pass

Turbidity

11 ± NTU

95.4%

99.1%

Pass

NSF/ANSI 401

Maximum 
Concentration 

Minimum 
Reduction 

Overall % 
Reduction

Results

Atenolol

30 ng/L

94.2%

94.2%

Pass

Bisphenol A

300 ng/L

98.80%

98.9%

Pass

Carbamazepine

200 ng/L

98.6%

98.6%

Pass

DEET

200 ng/L

98.7%

98.7%

Pass

Estrone

20 ng/L

96.30%

96.5%

Pass

Ibuprofen

60 ng/L

95.3%

95.4%

Pass

Linuron

20 ng/L

96.6%

96.6%

Pass

Meprobamate

60 ng/L

94.7%

94.7%

Pass

Metolachlor

200 ng/L

98.6%

98.6%

Pass

Naproxen

20 ng/L

96.3%

96.4%

Pass

Nonyl phenol

200 ng/L

97.50%

97.5%

Pass

Phenytoin

30 ng/L

95.50%

95.6%

Pass

TCEP

700 ng/L

98%

98%

Pass

TCPP

700 ng/L

97.8%

97.8%

Pass

Trimethoprim

20 ng/L

96.7%

96.7%

Pass

NSF P473

Influent 

challenge 

concentration

Maximum 

permissible 

product water 

concentration

Overall % 

reduction

Results

Perfluorooctanoic acid (PFOA) & 
Perfluorooctane sulfonate (PFOS)

1.5 ±10% ug/L 0.07 ug/L

96%

Pass

The AQ-RO3 has been tested and certified by NSF 
International against NSF/ANSI Standards 42, 53 
and 401 in model AQ-RO-3 for the reduction claims 
specified on the Performance Data Sheet as verified 
and substantiated by test data and at nsf.org.

The AQ-RO-3 has been tested and certified by 
NSF International against NSF/ANSI Standard 
58 for the reduction claims specified on the 
Performance Data Sheet as verified and 
substantiated by test data and at nsf.org.

AQ-RO-3_PDS_20171106

Performance Data for the OptimH2O™ Drinking Water System: Model AQ-RO-3

Replacement

Operating  

pressure range

Operating  

temp range

Recovery 

Rating

Efficiency 

Rating

Daily Produc-

tion (DPR)

AQ-RO3-RO, AQ-RO3-Carbon, 

AQ-RO3-Claryum

40-100 psi 

275-689 kPa

40-90° F 

4.44-32.2° C

29.43%

17.91%

13.32 gallons 

50.4 liters

Manufactured by: Aquasana, Inc.

 6310 Midway Road · Haltom City, Texas 76117 · 866.662.6885

Содержание OptimH2O AQ-RO-3

Страница 1: ...ter technology is working for you System tested and certified by NSF International against NSF ANSI Standard 42 53 401 and conforms to NSF protocol P473 for reduction of claims specified on the Perfor...

Страница 2: ...aucet hole to ensure there will be enough 3 8 tubing available for both connections Wait to cut tubing and follow instructions below 4 Remove system remineralizer and tank from under your sink to begi...

Страница 3: ...RO3 RO OptimH2O OptimH2O A B C D E F OptimH2O OptimH2O OptimH2O OptimH2O OptimH2O OptimH2O OptimH2O A B C 2 1 2 INSTALL SYSTEM MANIFOLD 1 Select an easily accessible area under the sink to mount syste...

Страница 4: ...cet 5 INSTALL RO DRAIN CONNECTOR WARNING CAUTION Be sure that all electrical appliances and outlets are turned off at the circuit breaker before working in the cabinet area Please wear safety glasses...

Страница 5: ...Membrane red tubing from faucet 1 Insert restrictor into the end of the red tubing 2 Attach red tubing to the 90 elbow until it stops 3 Attach 90 elbow to the membrane drain port VI Faucet to Drain C...

Страница 6: ...ing end If there are squarely cut 1 off and re insert Note When RO Filter System is first pressurized water may project from faucet air gap hole until air is passed from RO Filter System Purge 1 Open...

Страница 7: ...the scaling and fouling tendencies of the Feed Water 2 Measured at 50 psi 77 2 F and 717 mg l TDS per NSF ANSI Standard 58 3 Efficiency rating means the percentage of the influent water to the system...

Страница 8: ...y filled flush saturate the remineralizer cartridge by opening up the filter faucet and allowing the purified water to run through the remineralizer for 3 minutes The water may come out cloudy during...

Страница 9: ...oroethylene 0 007 0 083 0 001 99 cis 1 2 dichloroethylene 0 07 0 170 0 0005 99 trans 1 2 dichloroethylene 0 1 0 086 0 001 99 1 2 dichloropropane 0 005 0 080 0 001 99 cis 1 3 dichloropropylene 0 079 0...

Страница 10: ...hibit the exclusion or limit of incidental or consequential damages so the above limitation or exclusion may not apply to you WARRANTY CARD Warranty registration is not required for coverage under the...

Страница 11: ...s to NSF protocol P473 for reduction of claims specified on the Performance Data Sheet and at nsf org The AQ RO 3 system has been tested and certified by NSF International against NSF ANSI Standard 58...

Отзывы: