Models - ORP
CT
Series
C [x]
Series
S
Series
T
Series
A & P
Series
Options
Available
Not
Fitted
Oxidising
(Not
Visible)
Oxidising
(Not
Visible)
Oxidising/
Reducing
Oxidising
(Not
Visible)
Default Mode
Oxidising Oxidising
Oxidising Oxidising
Unsafe minimum
ORP warning
N/A
400
600
No
warning
500
Unsafe maximum
ORP warning
N/A
750
850
No
warning
850
Default Values
N/A
500
725
500
550
Table 2.
Set ORP Screen
Not Available on all Controllers. Refer to table 2. Adjacent.
Allows the user to set the ORP options for the controller.
SET:
[value from Table 2]
Options:
Value range of 0 to 999 mV.
Use arrow keys to cycle these
selections
DUTY:
[50%] = Pump Dose Duty.
Options: Values in the range of
1 to 100%. Use the arrows to
cycle these selections.
MODE: [FLOW]
Options: FLOW/CON/TIM/
OFF.
Use arrow keys to cycle these
selections.
ALM: [+/-]
Options:
+ (alarm if above specified
value)
- (alarm if below specified
value)
+/- (alarm if outside specified
range)
OFF (Alarm disabled)
Use arrow keys to cycle these
selections.
When the cursor is on one of the alarm modes press ENT to change
the numerical values associated with that alarm. Select from the
values of 25, 50, 100, 150, 200, 300, and 400. These values are the
range from the set point that will trigger an alarm. Press the ENT
again to move to the next set ORP item.
Alarm defaults: Min: 400 / Max: 750.
The controller has factory defaults which will issue alarms when
these values are exceeded.
LOCK: [OFF]
Options: (Preferred lockout period)
Value In the range of 10 to 990 minutes,
OFF - disabled
Use arrow keys to cycle these selections.
If the lockout time is greater than 10 the lockout function is active.
The controller will then “lock out” output after the selected time has
elapsed without the controller having reached its nominated set
point for ORP. This is a safety feature to prevent overdosage in
case of sensor failure.