![AQUALEAK EMS-10X Скачать руководство пользователя страница 36](http://html.mh-extra.com/html/aqualeak/ems-10x/ems-10x_instruction-manual_2960058036.webp)
Environmental Monitoring System (EMS-5X, 10X and OS) Instruction Manual
36
4.2.8
Interface Board and Outstation Settings
The Interface Board (i.e. Master Panel) and Outstations are configured the same way. As such,
both share the same attribute and profile folder names in the .xml configuration file.
The first (or only) Outstation profile will be for Interface Board configuration (
); the
second profile onwards are to configure Outstations.
The
Outstations
attribute folder contains element settings to configure the Interface Board (i.e. connected
to the master panel in the unit) and outstations (i.e. mounted elsewhere) zone inputs:
Figure 26:
Expanded Outstation profile Folder (First Profile for Interface Board)
Interface Setting
Description
ID
Identification number. Linked to the Internal station ID element used for relays 1-
10 in the
RelaySettings
attribute folder (see
Name
Default set to
ID1
.
Z1T, Z2T, Z3T, Z4T,
and Z5T
Sensor Alarm thresholds for each sensor on the internal station board. Range is from
0 (short circuit / leak)
to
255 (open circuit / cable break)
. Typically set to
80.
Adjust to a lower value of the sensor is in a very damp environment. Adjust to a
higher value if in a very dry area and/or very small leaks are to be detected.
Z1Name, Z2Name,
Z3Name, Z4Name,
and Z5Name (etc.)
Zone identities, e.g. Comms Room, Plant Room, Tea Point etc. Default is Zone 1,
Zone 2, Zone 3, etc.
Table 14:
Interface Board and Outstation Settings
Configure Interface Board and Outstation settings as follows:
1.
Click the icon next to the
Outstations
attribute folder and then the
Outstation
folder to expand them. All configurable
elements will appear below, along with
element text to change in the right column
(
2.
Click the
element
text to change
to
highlight
and edit as required (
3.
Once editing of the file is complete, update
the
configuration version
,
date
, and
author
. Use the XML or text editor
‘Save
As’ option to rename the file to the
updated version number.
Attribute
Folder
Element text to change
Interface
Board or
Outstation
profile