Environmental Monitoring System (EMS-5X, 10X and OS) Instruction Manual
34
B.
Relay 1 to 10 Configuration
Relays 1-10 are normally used to
trigger actions
(e.g. close a valve) in the event of an
alarm
. Each
relay may have up to
10 alarms
.
System components may be inactive for long periods of time. Exercising them will help keep the
entire system in best operational health, i.e. exercising a solenoid valve regularly will keep it
from seizing.
Relay 1-10 Settings
Description
Rel
ay 1
-10
El
eme
nts
Relay
Profile folder containing relay elements and the Triggers profile folder.
There may be up to 10 Relay folders (i.e. one for each configurable relay).
RelayID
Relay ID. Enter number of a relay to be operated (1-10).
RelayName
Relay Name (e.g. ‘
RelayLatched
Set to
1
to
latch Relay.
The relay will remain set until the alarm has cleared
and the Relay message in the Alarm List has been reset by the operator
(
section 5.4
).
Set to
0
to
disable.
The relay will de-energise once all Trigger alarms are
clear.
ExercisePeriod
Relay exercise period.
1
will exercise relays
every day
(
24 hours);
30
will
exercise relays every
30 days (720 hours)
.
Set to
0
to
disable
.
ExerciseTime
Relay exercise time. If
ExercisePeriod
is enabled, set in
24-hour format
(e.g. 00:00:00 will set the exercise time to midnight). When setting relay
exercising to operate at a certain time of day it is highly advisable to
staggering the relay operation times to avoid overloading the power supply
fuse and/or cause water hammer/surges.
ExerciseDuration
Relay exercise duration. If
ExercisePeriod
is enabled, set period of time
in
seconds
to exercise the relay (default is
60 seconds
).
Triggers
Profile folder that can contain up to
10
Trigger
folders. The relay can
therefore be triggered by up to
10 different alarms
from any sensor input
on any zone.
Trigger
Folder containing Interface board identification and Zone identification
elements to trigger the relay.
OutstationID
Interface board ID. Station number to trigger relay. Contained in the
Trigger
Folder
.
ZoneID
Zone ID. Sensor to trigger relay (e.g
shows Relay 1 will be
triggered by the Interface board, Sensor 1). Contained in
Trigger Folder
.
Table 13:
Relay 1
–
10 Settings
Configure a relay (1-10) as follows:
1.
Click the icon next to the
RelaySettings
attribute folder to expand it. All relay
profile folders and configurable elements
will appear below, along with
element
text
to change
in the right column (
2.
Click the
element
text to change
to
highlight
and edit as required (
3.
To set up
sensor triggers
(alarms) for the
relay, or another relay, see the instructions
below.
4.
Once editing of the file is complete, update
the
configuration version
,
date
, and
author
. Use the XML or text editor
‘Save
As’ option to rename the file to the
updated version number.