Environmental Monitoring System (EMS-5X, 10X and OS) Instruction Manual
49
B.
Reset Output Relay
Relays 1-5
are programmed to
latch
(i.e. activate) when their associated
zones
develop an alarm
condition (e.g. Zone 1 latches Relay 1, Zone 2 latches Relay 2, etc.). Relays must be reset
individually. There is a
log
After an Alarm has been
acknowledged
) and its associated
sensor
has
been dried, the output
relay
must be
unlatched
(i.e. reset).
Figure 39:
EMS Alarms Screen with Selected Relay and Reset Relay Button
Unlatch an output relay as follows:
1.
Open the
Alarms
screen (i.e. if on a
different screen).
2.
Tap a
relay
listed with a red background to
reset. The text colour will change from
black
to
blue
. A green
‘
Rest Relay
’
button
will also appear (bottom centre-left;
). A
numeric keypad
for the user
PIN will display.
3.
Enter a
user PIN
(default:
0000
;
4.2.3 User PIN Types and Numbers
configure PIN Numbers to any 4-digit code).
4.
The selected
relay
will be reset and turn
green
on the list. The ‘
Reset Relay
’
button
will also disappear.
5.
Tap the
‘
Refresh Alarm List
’
button to
clear the reset relay.
5.4.2
Mute Alarms
The Mute button will not silence
external sounders
wired through the system relays. This can only
be done by
acknowledging the alarm (
.
Mute the Master Panel’s internal buzzer as follows:
1.
Open the
Summary
screen
(i.e. if on a
different screen).
2.
Tap the amber
‘
Mute
’
button (
).
3.
Once complete, tap the ‘
Back
’
button to
return to the
Summary
screen
.
Selected Relay
Reset Relay
Button