![AQUALEAK EMS-10X Скачать руководство пользователя страница 39](http://html.mh-extra.com/html/aqualeak/ems-10x/ems-10x_instruction-manual_2960058039.webp)
Environmental Monitoring System (EMS-5X, 10X and OS) Instruction Manual
39
Part 1 of 3: Prepare the .apk software update as follows:
1.
Copy the
EMS software to install
(.apk file)
onto a
USB stick
.
2.
Ensure the EMS is powered ON and at the
Summary screen
. Open the front of the
Master Panel to access the USB Port located
at the rear of LCD display.
3.
If appropriate,
switch SW1
can be set to
the
ON
position to bypass the
reboot relay
(section
4.
Plug the
USB stick
into the
EMS USB port
.
Wait a few seconds for the USB stick to be
recognised.
Part 2 of 3: Install the .apk software update as follows:
1.
Summary
screen:
Tap ‘
Engineer
’
> Enter
Pin (
default 1234
) > Tap
‘Exit Application’
.
2.
EMS screen:
Tap the
Menu Icon
(i.e. the
circular button with 6 dots;
). The
Android Operating System menu will
appear, along with the
ASTRO File Manager
icon
.
3.
Tap the
ASTRO File Manager icon
(
Figure
23
). The ASTRO File Manager screen will
appear, and the USB disk will be opened
automatically.
4.
Tap the
.apk software update icon
to
install (
5.
A
‘Complete action using’ dialog box
will
appear. Tap
‘Package Installer’
and then
‘Just Once’
6.
A
confirmation dialog box
will appear. Tap
‘Install’
to confirm and begin installation
7.
After a while, the confirmation dialog box
will state that the .apk software update has
been successfully installed
(
8.
If the confirmation dialog box does not
close automatically, tap
‘Done’
to close it
). The EMS will return to the
ASTRO File Manager screen
.
Part 3 of 3: Finalise the .apk software update as follows:
1.
ASTRO File Manager screen:
Tap the
three
dots
in the
top bar
located in the
right-
hand corner
. A drop-down menu will
appear (
2.
Tap
Exit
in the drop-down menu to leave
the ASTRO File Manager and return to the
Android menu
.
3.
Tap the
EMS icon
to load the new .apk
software update.
4.
The procedure for loading new software
onto the EMS Main Panel is now complete.
Ensure
switch SW1
is set to the
OFF
position (see
). Remove