41
User manual S200 WCS
Update August 2021
11 Sensor
– Actuator Bus (MODBUS RTU)
The S200 measuring and control device is equipped with a sensor - actuator bus.
The MODBUS RTU protocol is used.
The hardware is a RS 485 interface.
Shielding = terminal 94
A = + terminal 93
B = - terminal 92
+12V = terminal 91
0V = terminal 90
A max. load of 200mA is allowed for the 12V power supply.
11.1 Shielding
The use of shielded cables offers a high protection against electromagnetic interference,
especially against high frequencies. However, the effectiveness of the shielding is dependent
on a careful installation of the cable.
The shielding is placed near the ModBus master.
11.2 Communication parameters
Baud rate:
9600 bps
Data bits:
8
Start bits:
1
Stop bits:
1
Parity:
no