DEFROST1 SENSOR OPEN
or
DEFROST2 SENSOR OPEN
ISSUE
Open defrost sensor.
RESOLUTION
A qualified technician should replace the defrost sensor.
DEFROST1 SENSOR SHORT
or
DEFROST2 SENSOR SHORT
ISSUE
Shorted defrost sensor.
RESOLUTION
A qualified technician should replace the defrost sensor.
ERROR AT PRIMARY UNIT
ISSUE
The heat pump is secondary to a primary heat pump that is displaying a fault code.
RESOLUTION
The error at the primary heat pump must be corrected before the secondary unit will resume operation.
HIGH PRESSURE FAULT
ISSUE
The refrigerant system’s high-pressure switch is showing as open.
RESOLUTION
Heat and Cool Units (Reversing)
Place heat pump in heating mode and perform the following troubleshooting.
Determine if an insufficient amount of water is being supplied to the equipment.
1. Confirm the filter pump is on.
2. If a multiple-speed filter pump is being used, run filter pump at a higher speed. Do not exceed the
maximum flow rate for the model.
3. Confirm water is not being diverted away from the heat pump.
l
l
Adjusting Water Flow Using ΔT (Delta-T)
HIGH WATER TEMP
ISSUE
Incoming water temperature has exceeded 108° F (42° C) and the unit has been deactivated. The heat
pump will not operate until the incoming water temperature drops to 100° F (38° C) or lower.
RESOLUTION
1. Determine if a gas heater is sending water directly to the heat pump. This situation would need to be
corrected before continuing.
2. If the
HIGH WATER TEMP
fault continues to display, the water temperature sensor may require
replacement.