Simpool pH model
INSTRUCTION AND MAINTENANCE MANUAL
Programmable digital peristaltic pump
ENGLISH
ADSP7000407
rev. 1.2
27/03/2015
45/313
2.3.1 ASSEMBLY OF THE ACCESSORIES
The probe-holder is installed on a D50 or D63 diameter tube on which a 24 mm diameter hole has been
carried out;
Check the direction of the flow in the tube to insert the injection tube correctly;
The probe-holder must be positioned vert- 45°
Performing a D24 mm hole
Conduct a 5 mm pre-hole at the centre of the upper part of the tube;
Expand the hole with the 24mm drill bit supplied in the installation kit, until you introduce the whole
drill bit in the tube;
Deburr the hole by removing the PVC residues;
Installing the probe-holder:
Insert the O-ring on the small injection tube;
Insert the small injection tube on the tube by following the direction of the flow, as indicated by the arrow on
the label;
Position the O-ring in place and hold it there. Apply the upper part of the probe-holder on the pool tube;
Insert the two screws (if it is a DN63 tube use the two spacers between the upper probe-holder and the
lower collar). Apply the lower part of the probe-holder on the tube and tighten the nuts on the screws;
Screw the clamping screws evenly to achieve proper fastening. Do not tighten a screw fully home
when the other one is still unscrewed.
Fig. 2- Probe-holder Assembly
Installing the short electrode
6. Remove the cap from the electrode. (
Carefully store away the cap
, you will need it during maintenance or
when the equipment is not used during winter. In this case, it must placed back on the electrode after filling
it up to ¾ with water);
7. Insert the two O-rings and slide them until they reach the lower part of the electrode's head;
8. Pass the electrode's cable on the slot located on the ring nut;
9. Now go ahead with the calibration of the probe described in chapter 3.3.3 and then proceed with section 5;
10. Insert the electrode in the probe-holder without forcing it in until the O-ring positions itself between the
lower part of the electrode head and the seat on the probe-holder. Then tighten the ring nut manually;
Refer to Fig. 3