Simpool pH model
INSTRUCTION AND MAINTENANCE MANUAL
Programmable digital peristaltic pump
ENGLISH
ADSP7000407
rev. 1.2
27/03/2015
58/313
Select the
P.P.b
value of the pH Proportional Band: to enter and exit the submenu use
Enter,
to scroll
through the 0.5/ 1/ 1.5/ 3 values use the
▲
and
▼ keys;
Set the
PHP
value in seconds of the duration of the pH Cycle Period: to enter and exit the submenu, use
Enter,
to scroll through the values from 300 to 999 seconds use the
▲
and
▼ keys;
Set the minimum
A.PH
variation of the pH to activate the OFA alarm within a range of 0.05- 0.99 pH: to
enter and edit the submenu use
Enter,
to scroll through the values use the
▲
and
▼ keys;
Set the minimum variation of the pH to reset the OFA alarm,
r.PH
within a range of 0.99-90 mV: to enter and
exit the submenu use
Enter,
to scroll through the values use the
▲
and
▼ keys;
Select the time frame to control the OFA alarm,
OFA
, within a range of 300-999 seconds or disable it (
OFF
):
to enter and exit the submenu use
Enter,
to scroll through the values use the
▲
and
▼ keys;
Set the stabilization time of the inhibiting signal,
Stb
, coming from the pool's circulation pump in a range of
0- 999 seconds: to enter and exit the submenu use
Enter,
to scroll through the values use the
▲
and
▼
keys;
Set the time of the pump's maintenance alarm,
O.F.d
, from 0 (disabled) to 999 hours, based on the following
format:
-
h.mm
up to 9 h and 59 m
-
hh.m
up to 99 h and 59 m (minutes expressed in tens)
-
hhh
up to 999 h
To enter and exit the submenu use
Enter
and increase/decrease the value with the
▲
and
▼ keys;
Access the window to identify the inhibiting signal,
S.In
: to enter and exit the submenu use
Enter
. The
display will show the status identified by the pump for the input signal:
steady “HI”
: enabling signal identified as active;
steady “Lo”
: enabling signal identified as not active;
flashing “HI”:
enabling signal identified as active, but just above the identification voltage threshold;
flashing “Lo” :
enabling signal identified as not active, but just below the identification voltage threshold;
If the status displayed does not correspond to the actual status of the signal or if the status displayed is
flashing, just scroll with the
▲
and
▼ keys to change the threshold, namely:
Status of the non-active signal (recirculation pump OFF)
if the signal is identified as active (
HI
steady or flashing) or not active but near the threshold (flashing
Lo
),
press ▼ to reduce the threshold voltage until a steady “
Lo
” is displayed;
if the signal is permanently identified as not active (steady
Lo
), conduct a check when the signal is
activated;
Status of the non-active signal (recirculation pump ON)
if the signal is identified as not active (
Lo
steady or flashing), or active but near the threshold(
HI
flashing),
press
▲
to increase the threshold voltage until a steady “
HI
” is displayed;
if the signal is permanently identified as not active (steady
HI
), conduct a check when the signal is
disabled;
Enable or do not enable the acquisition of the inhibiting signal to read and adjust the pH,
A.In:
to enter and
exit the submenu use
Enter,
to scroll through “
YES/no
” use the
▲
and
▼ keys;
Choose if you want to make the Setpoint,
OnS
, a value that can be changed from the User Menu: to enter
and exit the submenu use
Enter,
to scroll through “
YES/no
” use the
▲
and
▼ keys;
Choose if you want to make the pH operating mode,
Ond
, a value that can be changed from the User Menu:
to enter and exit the submenu use
Enter,
to scroll through “
YES/no
” use the
▲
and
▼ keys;
Choose if you want to calibrate the pH probe from the User Menu,
OnC
: to enter and exit the submenu use
Enter,
to sc
roll through “
YES/no
” use the
▲
and
▼ keys;
Choose if you want to modify the temperature value from the User Menu,
Ont
: to enter and exit from the
submenu use
Enter,
to scroll through “
YES/no
” use the
▲
and
▼ keys. This entry is displayed only if the
temperature is set in manual mode from the Programming Menu;