© 2014  New Aqua LLC dba Aqua Systems  •  7785 East US Hwy 36 • Avon, IN 46123

6

Eradicator II AIF Systems

Installation, Operation,and

Maintenance Manual

Location Data

Sizing Information:

Hardness ______ grains per gallon

Iron          ______ parts per million

pH           _______                        

Chlorine  ______  parts per million

Inlet Water Line Size ______

No. in Family _______

No. Baths  _________

Bypassed Hard Water Lines:

Outside Spigots       ___________

Swimming Pool Fill Line ________

Kitchen Cold _________________

Irrigation Systems_____________

Pre Install Review

Requirements for Proper Operation:

Tips:

Water Pressure:

  The system requires a minimum of 20 psi 

to be sustained with flowing water of 5 gallons per minute or 

greater.  Maximum is 125 psi.

Flow Rate:

  A minimum of 5 gallons per minute is required 

for proper operation.  If less than 5 gallons per minute is 

available, consult with your dealer for possible custom 

configurations.

Water Temperature:

  The range of water temperature for 

these systems is 40˚ F to 110˚ F.

Drain:

 A drain within 20’ of the system can be run with

1/2

” tubing.  Drains running over 20’ should use 

3/4

” tubing.  

Maximum overhead rise should be ≤ 8’.  Consult your dealer 

for any drain > 30’ in length.

Special Drain Note:

  The drain must be a legal connection 

with a code compliant air gap.  It is critical that the drain be 

secured tightly at each end, and anchored throughout the run.  

The AIF systems will jolt the drain line during the release of 

air.  Be sure to protect the immediate area from any spray 

that may occur at the air gap.  The drain connections should 

be thoroughly tested before completing the installation.

Electricity:

  An uninterrupted 110volt A.C. source is required 

to operate AIF systems.

Special Electrical 

Note: 

You  must  make  sure  that  the 

power

outlet is not connected to a timer, or a switch.

Source water pH:

  If the pH of the source water 

is < 7, you must consult with your dealer.  The 

pH adjustment option must be added if pH is 

below this specification.

Freezing:

   The AIF  system,  drain,  plumbing 

and all other water fixtures, must be protected 

from freezing temperatures.  Be sure that the 

installation site is not exposed to temperatures 

below 32˚ F.

Positioning:

    Be  sure  to  position  the AIF 

system so it can be removed or accessed for 

future servicing.

Outside Faucets:

  Outside faucets must be 

bypassed from any AIF system.  These systems 

are  not  designed  for  watering  lawns,  filling 

pools, or any other outdoor use.

Sand:

  If sand or sediment is present you must 

install a sand separator, or sediment filter ahead 

of the AIF system.

Chlorine:

  AIF systems will not work on chlo-

rinated  water  supplies.  Chlorine,  and  other 

strong oxidizers will damage the media bed in 

AIF iron filters.

Содержание Eradicator II AIF

Страница 1: ...6123 1 Eradicator II AIF Systems Installation Operation and Maintenance Manual Eradicator II AIF Air Induction Filter Systems Installation Operation and Maintenance Manual 114 Vista Parkway Avon IN 46...

Страница 2: ...fundamentals of the product line and the standard models However it is possible that your AIF system was designed to be site specific Refer to the model number if you have questions for your system p...

Страница 3: ...r Proper Operation 6 Location Data 6 Pre Assembly 7 Bypass Operation 8 Installation 9 11 AIF Placement 9 Start Up 12 Programming 13 15 Service 16 Parts Diagrams 18 27 Service Guide 28 Drive Assembly 2...

Страница 4: ...olume Air is inducted to system before returning to the treatment cycle Water in passes through air head Treated water exits through distributor Water inlet is reversed in backwash cycle Air water to...

Страница 5: ...must include the pH adjustment option when treating iron The water supply must have adequate flow and pressure to backwash the applied system Be sure to reference the required backwash rate of a spec...

Страница 6: ...tion with a code compliant air gap It is critical that the drain be secured tightly at each end and anchored throughout the run The AIF systems will jolt the drain line during the release of air Be su...

Страница 7: ...nt to the plumbing system The bypass is designed to accommodate minor plumbing misalignments but is not designed to support the weight of a system or the plumbing figure 1 Connection ports on back of...

Страница 8: ...le not allowing water to exit from the con trol valve to the plumbing see figure 3 4 Shut Off Position The inlet handle points to the center of the bypass valve and the outlet handle points in the dir...

Страница 9: ...ng and o ring Heat from soldering or solvent cements may damage the nut split ring or o ring Solder joints should be cool and solvent cements should be set before installing the nut split ring and o r...

Страница 10: ...let and outlet pipes to retain continuity of the plumbing 8 Connect the drain on the AIF system to an approved air gap drain When using the 5 8 poly tubing for the drain line con nect the nut to the l...

Страница 11: ...ater Conditioner Drain with code air gap connection Untreated water Bypass Outside spigots Filtered Hard Water Bypass Water Heater 12 of pipe between softener and heater 3 Valve Bypass Optional Well L...

Страница 12: ...amount of time You must let the system complete the air induction cycle which will be 30 40 minutes depending on the system size 5 Once the air induction cycle has been completed the Eradicator contr...

Страница 13: ...rent Time hour Set the hour of the day using Up or Down buttons AM PM toggles after 12 Press NEXT to go to step 3 3 Current Time minutes Set the minutes of the day using Up or Down buttons Press NEXT...

Страница 14: ...Up or Down buttons Press NEXT to set energy saver 5 Energy Saver Use the Up or Down buttons to activate or cancel the energy saver OFF Backlight always on ON Back light off after 5 minutes of inactivi...

Страница 15: ...s for it usually referred to as manual regeneration There may be a period of heavy water usage because of guests or a heavy laundry day 4 To initiate a manual regeneration immediately press and hold t...

Страница 16: ...se you may pull the system away from the plumbing see note at right 8 With the system off of the plumbing you can loosen the base nut to remove the valve from the media tank see figure 2 Service Make...

Страница 17: ...g clip see page 16 figure 1 8 Insert the Drain line into it s position and install the lock clip see page 16 figure 1 9 Plug unit into the electrical outlet 10 Press Next and Regen buttons to reset co...

Страница 18: ...F Systems Installation Operation and Maintenance Manual Parts Diagrams Quick Connect Assembly No Part No Description Qty 1 02910182 Tank Adapter items 1 4 1 2 02910183 Tank Nut 1 3 02910184 Split Ring...

Страница 19: ...Part No Description Qty 1 02910301 SCII Front Cover Assy 1 2 02910128 Motor 1 3 02910127 Drive Bracket and Spring Clip 1 4 02910300 SCII ALX PC Board 1 or 02910299 SCII AQX PC Board 1 5 02910132 Drive...

Страница 20: ...s Installation Operation and Maintenance Manual Parts Diagrams Quick Connect Assembly No Part No Description Qty 1 02910111 Spacer Stack Assy 1 2 02910110 Drive Cap Assy 1 3 02910141 O Ring 228 1 4 02...

Страница 21: ...Screen 1 4 02910123 Injector Assy Z Plug 1 02910112 Injector Assy A Black 02910113 Injector Assy B Brown 02910114 Injector Assy C Violet 02910115 Injector Assy D Red 02910116 Injector Assy E White 5...

Страница 22: ...ms Installation Operation and Maintenance Manual Parts Diagrams Air Injection Port No Part No Description Qty 2 03310730 Elbow Locking Clip 1 3 03310738 Polytube Insert 3 8 1 4 03310732 Nut 3 8 1 5 03...

Страница 23: ...Insert 5 8 1 3 02950121 Nut 3 4 Drain Elbow 1 4 02910152 Drain Elbow 3 4 Male Assy 1 5 02910154 O Ring 019 1 6 02910153 DLFC Retainer Assy 1 02950124 DLFC 0 7 gpm for 3 4 02950125 DLFC 1 0 gpm for 3 4...

Страница 24: ...IN 46123 24 Eradicator II AIF Systems Installation Operation and Maintenance Manual Parts Diagrams Meter Assy No Part No Description Qty 1 02910148 Nut 1 QC 1 2 02910108 Meter Assy 1 3 02910140 Turbin...

Страница 25: ...cription Qty 1 02910148 Nut 1 Quick Connect 2 2 02910147 Split Ring 2 3 02910126 O Ring 215 2 4 02910146 Fitting 1 PVC Male NPT Elbow 2 Not Shown 22302027 Test Port Valve 1 02950002 Complete PVC Male...

Страница 26: ...1 Quick Connect 2 2 02910147 Split Ring 2 3 02910126 O Ring 215 2 4 02910142 Bypass 1 Rotor 2 5 02910143 Bypass Cap 2 6 02910187 Bypass Handle Gray 2 7 02910144 Bypass Rotor Seal Retainer 2 8 0291014...

Страница 27: ...LLC dba Aqua Systems 7785 East US Hwy 36 Avon IN 46123 27 Eradicator II AIF Systems Installation Operation and Maintenance Manual Parts Diagrams Valve Wrench No Part No Description Qty Shown 02950123...

Страница 28: ...the drive bracket start by removing the plugs for the power source and the water meter Unweave the wires from the side holders Two tabs on the top of the drive back plate hold the drive bracket in pla...

Страница 29: ...d hold NEXT and REGEN buttons for 3 seconds or unplug power source jack black wire and plug back in This resets the electronics and establishes the service piston position The display should flash all...

Страница 30: ...ack o ring on the spacer stack assembly is no longer visible through the drain port Spacer Stack Assembly To access the spacer stack assembly remove the drive assembly drive cap assembly and piston Th...

Страница 31: ...combination of the up flow main piston and the regenerant piston or c for backwash only systems a plug is in the DN hole and in the UP hole and that the piston only has a down flow main piston the re...

Страница 32: ...orward on the turbine to remove it from the shaft Do not use a wire brush to clean Wipe with a clean cloth or chemically clean in dilute sodium bisulfite or vinegar The turbine can be immersed in the...

Страница 33: ...heir correct orientation To install the gray arrow handles correctly keep the handles pointed in the same direction as the arrows engraved on the control valve body while tightening the bypass valve c...

Страница 34: ...d Check control valve set up procedure regen eration time option e Control valve set at NORMAL on 0 e Check control valve set up procedure regen eration time option 5 SYSTEM ERROR Red Screen showing E...

Страница 35: ...and held a Transformer unplugged a Connect transformer b No electric power at outlet b Repair outlet or use working outlet c Broken drive gear or drive cap as sembly c Replace drive gear or drive cap...

Страница 36: ...r reaches the water heater it may take several days to flush out Water usage during regeneration can result in consistent or intermittent break through of iron and or sulfur Be sure that water using a...

Страница 37: ...2014 New Aqua LLC dba Aqua Systems 7785 East US Hwy 36 Avon IN 46123 37 Eradicator II AIF Systems Installation Operation and Maintenance Manual Installation Operation and Maintenance Manual Notes...

Страница 38: ...2014 New Aqua LLC dba Aqua Systems 7785 East US Hwy 36 Avon IN 46123 38 Eradicator II AIF Systems Installation Operation and Maintenance Manual...

Страница 39: ...2014 New Aqua LLC dba Aqua Systems 7785 East US Hwy 36 Avon IN 46123 39 Eradicator II AIF Systems Installation Operation and Maintenance Manual...

Страница 40: ...2014 New Aqua LLC 2 2014 Rev 1...

Отзывы: