LINKING PARALLEL DC OUTPUT

2W

310XAC

320XAC

340XAC

360XAC

Linked Units

2 - 3 Units, 1 2W (L1 - N )

Voltage

Line

0 - 420 V

5 - 420 V

Power

# Units

2

1.6 KVA

3.2 KVA

6.4 KVA

9.6 KVA

Max

3

2.4 KVA

4.8 KVA

9.6 KVA

14.4 KVA

Max Current

5 - 210 V 

L(2) 

7.68 A @ 210 V 

15.36 A @ 210 V 

30.72 A @ 210 V

46.08 A @ 210 V

L(3) 

11.52 A @ 210 V 

23.04 A @ 210 V 

46.08 A @ 210 V

69.12 A @ 210 V

5 - 420 V 

H(2) 

3.84 A @ 420 V

7.68 A @ 420 V 

15.36 A @  420 V

23.04 A @ 420 V

Line

H(3) 

5.76 A @ 420 V 

11.52 A @ 420 V 

23.04 A @  

420 V

34.56 A @ 420 V

MEASUREMENT (Total)*

LINKING PARALLEL  1 2W

310XAC

320XAC

340XAC

360XAC

Voltage

Range

0.0 -  400.0 V

Resolution

0.1 V

Accuracy

± (1% of r 2 counts) > 5 V

± (1% of r  5 counts) > 5 V

Frequency

Range

0.0 - 1000.0 Hz

Resolution

0.1 Hz

Accuracy

L

± 0.1 Hz @ 0.0 - 500 Hz

H

± 0.2 Hz @ 501 - 1000 Hz

Current (rms)

Range

2

0.00 A - 26.00 A 

0.00 A - 52.00 A 

0.00 A - 104.0 A

0.00 A - 156.0 A

3

0.00 A - 39.00 A 

0.00 A - 78.00 A 

0.00 A - 156.0 A

0.00 A - 234.0 A

Resolution

0.01 A

0.1A <= 99.99A, 0.01A > 100.0A

Accuracy

L

± (1.5% of r 15 counts) x # of

Linked Units @ 40 - 70 Hz & Current

is > 1.00 A

H

± (1.5% of r 15 counts) x # of

Linked Units @ 70.1 - 1000 Hz &

Current is > 5.00 A

± (1.5% of

r

15counts)× Link

Units at 40 -

70Hz, and

current(r.m.s) >

2.00A

± (1.5% of

r

15counts)× Link

Units at 70.1 -

1000Hz, and

current(r.m.s) >

10.00A

± (1.5% of r

15counts)× Link Units at

40 - 70Hz, and

current(r.m.s) > 3.00A

± (1.5% of r

15counts)× Link Units at

70.1 - 1000Hz, and

current(r.m.s) > 15.00A

Power (W)

Range

2

0 W - 2600 W

0 W - 5200 W

0 W -10400 W

0 W - 15600 W

3

0 W - 3900 W

0 W - 7800 W

0 W - 15600 W

0 W - 23400 W

Resolution

1 W

Accuracy

± (2% of r 10 counts) x (# of Linked Units) at PF   0.2, 40 - 500 Hz, and
Current > 5.0 A
± (2% of r 10 counts) x (# of Linked Units) at PF   0.3, 501 - 1000 Hz, and
Current > 5.0 A

Power Apparent
(VA)

Range

2

0 W - 2600 VA

0 W - 5200 VA

0 W -10400 VA

0 W - 15600 VA

3

0 W - 3900 VA

0 W - 7800 VA 

0 W - 15600 VA

0 W - 23400 VA

Resolution

1 VA

Accuracy

V x A, Calculated Value

Содержание 310XAC

Страница 1: ...ar AC Power Source Operation Manual for Models 310XAC 320XAC 340XAC 360XAC Ver 1 04 PART 39101 Associated Power Technologies Inc Telephone 1 909 860 1646 1142 S Diamond Bar Blvd 106 Fax 1 909 860 2727...

Страница 2: ...4 4 2004 IEC 61000 4 5 2001 IEC 61000 4 6 2003 IEC 61000 4 8 1993 A1 2000 IEC 61000 4 11 2004 Supplementary Information The product herewith complies with the requirements of the Low Voltage Directiv...

Страница 3: ...on the Instrument 34 4 1 1 Set Screen Description 35 4 1 2 Security 36 4 1 3 Lock 37 4 1 4 Mem Lock 37 4 2 System Parameters Description 38 4 3 Editing System Parameters 41 4 3 1 Editing Auto Run Mode...

Страница 4: ...4 6 13 Editing Timer Unit PROGRAM Mode only 73 4 6 14 Editing Delay PROGRAM Mode only 73 4 6 15 Editing Dwell PROGRAM Mode only 74 4 6 16 Editing Ramp Down PROGRAM Mode only 75 4 6 17 Editing Step Cy...

Страница 5: ...nfiguration 104 9 1 3 Sending and Receiving Commands 105 9 2 GPIB Interface 105 9 2 1 GPIB Connector 105 9 2 2 GPIB Address 106 9 3 Interface Functions 106 9 4 GPIB RS 232 Interface Command List 107 9...

Страница 6: ...4 1 Ethernet Card Setup 130 11 4 2 Saving New Settings 132 11 4 3 Power Up 132 11 4 4 Ethernet Card Menu 134 11 4 5 IP Setup 134 11 4 6 IP Address 134 11 4 7 Gateway IP 135 11 4 8 Subnet Mask 135 11...

Страница 7: ...trument Parts used must be parts that are recommended by APT as an acceptable specified part This warranty does not cover accessories not of Associated Power Technologies Inc manufacture Except as pro...

Страница 8: ...er the vector sum of the real and reactive power components of a circuit Measured in VA volt amps Direct Current DC current that only flows in one direction Direct current comes from a polarized sourc...

Страница 9: ...and complex power Power factor The ratio of real power watts to apparent power VA Based on a scale from 0 to 1 to determine how reactive and resistive a load is Reactive Power the power absorbed by ca...

Страница 10: ...uctions before operation To prevent accidental injury or death these safety procedures must be strictly observed when handling and using the test instrument 1 4 Service and Maintenance User Service To...

Страница 11: ...nty APT will not be responsible for any injuries sustained due to unauthorized equipment modifications or use of parts not specified by APT Instruments returned to APT with unsafe modifications will b...

Страница 12: ...save the shipping carton and packing material for the carrier s inspection Our customer support department will assist you in the repair or replacement of your instrument Please do not return your pr...

Страница 13: ...13 320XAC 340XAC...

Страница 14: ...switch or circuit breaker for disconnecting it from each operating energy supply source In compliance with EN61010 1 for permanently connected equipment this switch should meet the following guideline...

Страница 15: ...B C Ground Line Neutral Ground Nsense Lsense 2W 10 AWG 10 AWG 10 AWG 3W 12 AWG N A 12 AWG 4W 14 AWG 14 AWG 14 AWG 8 AWG 8 AWG 8 AWG 18 AWG 18 AWG 2 2 3 Power Cable Before connecting power to this ins...

Страница 16: ...ting Environment Temperatures 0 40 C 32 104 F Relative humidity 20 80 Altitude 2 000 meters 6 562 feet The instrument should also be protected against temperature extremes which may cause condensation...

Страница 17: ...over the instrument and also secured to the side Mark the container FRAGILE to ensure proper handling For all other models if you do not have the original packaging materials please follow these guid...

Страница 18: ...1 3W or 3 4W THD 1 Resistive Load at output voltage 80 140 V 160 280 V 1 5 Resistive Load at 501 1000Hz and output voltage within the 100 140Vac at Low Range or the 160 280Vac at High Range Crest Fac...

Страница 19: ...2 of reading 5 counts at PF 0 2 2 of reading 5 counts at PF 0 2 Power Apparent VA Range L 0 0 VA 120 0 VA 0 0 VA 240 0 VA x x H 100 VA 1300 VA 200 VA 2600 VA 0 VA 5200 VA 0 VA 7800 VA Resolution L 0...

Страница 20: ...reading 5 counts 5 V Voltage Hi Lmt AC 0 0 V 300 V 5 0 V 300 V DC 0 0 V 420 V 5 0 V 420 V Voltage Lo Lmt AC 0 0 V 300 V 5 0 V 300 V DC 0 0 V 420 V 5 0 V 420 V Frequency Hi Lmt Range 40 0 1000 Hz Frequ...

Страница 21: ...0 10 00 Timer Unit Second Minute Hour Ramp Up Range AC 0 00 999 9 DC 1 0 999 9 0 OFF Resolution 0 1 second minute hour Accuracy 0 1 0 05 sec Delay Range 0 5sec 999 9 sec 1 0 999 9 when linked 0 1 min...

Страница 22: ...Operation Key Feature Soft key Numeric Key Rotary Knob Remote Output Signal Output Pass Fail Test in Process Calibration Front Panel Key Lockout Soft Key Password Protected Synch Output Signal 5 V DC...

Страница 23: ...40 V 44 16 A 20 V and 240 V Line H 3 11 04 A 20 V and 240 V 22 08 A 20 V and 240 V 44 16 A 20 V and 240 V 66 24 A 20 V and 240 V LINKING POLY PHASE AC OUTPUT 3W 310XAC 320XAC 340XAC 360XAC Linked Unit...

Страница 24: ...A 3 0 00 A 39 00 A 0 00 A 78 00 A 0 00 A 156 0 A 0 00 A 234 0 A Resolution 0 01 A 0 1A 99 99A 0 01A 100 0A Accuracy L 1 5 of reading 15 counts x of Linked Units 40 70 Hz Current is 1 00 A H 1 5 of re...

Страница 25: ...G PARALLEL 1 2W 310XAC 320XAC 340XAC 360XAC Power Reactive Q Range 2 0 W 2600 VAR 0 W 25200 VAR 0 W 10400 VAR 0 W 15600 VAR 3 0 W 3900 VAR 0 W 7800 VAR 0 W 15600 VAR 0 W 23400 VAR Resolution 1 VAR Acc...

Страница 26: ...1 A X X H 0 01 A Accuracy 1 of reading 5counts at 40 70Hz 1 of reading 5counts at 70 1 500Hz and output current r m s 0 200A 1 of reading 5counts at 501 1000Hz and output current r m s 0 300A Power W...

Страница 27: ...ge A VAR B VAR C VAR Resolution 1 VAR Accuracy Calculated Value Power Factor Range 0 1 000 Resolution 0 001 Accuracy Sum P Sum VA Calculated and displayed to three significant digits MEASUREMENT Total...

Страница 28: ...4 Number Keypad Keys used to enter numerical data 5 Delete Key Used to delete text characters and numerical data 6 Rotary Knob Used to adjust the voltage output in MANUAL Mode or DC Mode 7 Lock Key U...

Страница 29: ...ctor for connecting the instrument to a master power source Connecting the interface cable to this port automatically designates the instrument as a slave unit 4b Interface Output Interface output con...

Страница 30: ...erminal Neutral output screw terminal 6d Ls Line voltage sense screw terminal 6e Ns Neutral sense screw terminal 7 Input Terminal Power Block provides input power to the instrument Model 340XAC requir...

Страница 31: ...rminal Power Block provides input power to the instrument Model 360XAC requires 180 264 VAC 1 180 264 VAC 3 or 312 457 VAC 3 at 47 63 Hz 11 Output Terminal Power Block provides output power to the DUT...

Страница 32: ...s settings and parameters Exit Allow you to exit the current screen Name Allow you to name a memory List Allows you to see the list of memories available Allows you to scroll through the list sequenti...

Страница 33: ...setting Next Allows you to scroll to the next parameter setting Change Allows you to open up the parameter for changing Result Allows you to open up the results screen System Allows you to open up th...

Страница 34: ...a few seconds the Initialization screen will change to the Set screen The Set screen will be displayed as follows when in PROGRAM Mode If you press the more soft key within the Set screen the soft ke...

Страница 35: ...Description of Parameters M1 1 Memory and step location 1 0s Instrument timer for output F 60 0 Hz Frequency Ap Peak Current Set Status of instrument at the present time Possible readings are set dwel...

Страница 36: ...e the password to access them Press and hold the top soft key while powering up the instrument the Edit Password screen should now be displayed The display will appear as follows You may now type in t...

Страница 37: ...ft key Press the System soft key Highlight the Lock parameter using the soft keys When the Lock parameter is highlighted you may turn the function ON and OFF by pressing the Change soft key Press the...

Страница 38: ...difference is that in MANUAL Mode the operator cannot connect steps or have fixed testing times The output is either ON or OFF in the MANUAL Mode 2 Out Mode configures the instrument for AC or DC volt...

Страница 39: ...r to select a maximum voltage threshold or ceiling level when programming the output voltage in the testing parameters screen 9 V Lo Lmt MANUAL Mode allows the operator to select a minimum voltage thr...

Страница 40: ...sensing If internal is selected the instrument will measure the output voltage at the output relay If external is selected the user must connect sensing wires from the Ls and Ns terminals located on r...

Страница 41: ...en will look as follows If the system parameters are set to MANUAL Mode the screen will look as follows Use the soft keys to navigate through the System parameters Press the Edit soft key to select th...

Страница 42: ...cancel the editing of the Auto Run Mode press the Esc soft key When the Enter soft key is pressed the Auto Run Mode is accepted and you transition into the next system parameter Out Mode 4 3 2 Editing...

Страница 43: ...mode that can be programmed into the instrument Press the Change soft key to toggle the Single Step Mode to ON OFF To save the parameter press the Enter soft key To cancel the editing of the Single St...

Страница 44: ...s the status of the contrast setting that is programmed into the instrument Contrast Range indicates the contrast range that can be programmed into the instrument Use the numeric keypad to enter in th...

Страница 45: ...ess the Change soft key to toggle the Power UP Mode to ON OFF LAST To save the parameter press the Enter soft key To cancel the editing of the Power Up feature press the Esc soft key When the Enter so...

Страница 46: ...turn to the System parameter screen When the Enter soft key is pressed the Loop Cycle Mode is accepted and you transition into the next system parameter 4 3 8 Editing V Hi Lmt V Lo Lmt MANUAL Mode onl...

Страница 47: ...v or Next soft key 4 3 9 Editing F Hi Lmt F Lo Lmt MANUAL Mode only Use the soft keys to navigate to the F Hi Lmt or F Lo Lmt parameter only selectable for AC output Pressing the Edit soft key will pr...

Страница 48: ...key 4 3 10 Editing Start and End Angle MANUAL Mode only Use the soft keys to navigate to the Start Angle or End Angle parameter only selectable for AC output Pressing the Edit soft key will provide o...

Страница 49: ...instrument The Results Modes available are ALL P F or LAST The ALL mode will show all the testing results after the test is completed The P F mode will show only a pass fail banner after the test is c...

Страница 50: ...you wish to bypass editing this parameter and move to the next parameter you can press the Prev or Next soft key 4 3 13 Editing OC Fold Use the soft keys to navigate to the OC Fold parameter Pressing...

Страница 51: ...Lock Modes available are ON and OFF Press the Change soft key to toggle the mode to ON or OFF To save the parameter press the Enter soft key To cancel the editing of the Lock Mode press the Esc soft k...

Страница 52: ...arameter you can press the Prev or Next soft key 4 3 16 Editing Volt Sense Use the soft keys to navigate to the Volt Sense parameter Pressing the Edit soft key will provide the following screen Volt S...

Страница 53: ...y To cancel the editing of the Sync Signal Mode press the Esc soft key When the Enter soft key is pressed the Sync Signal Mode is accepted and you transition into the next system parameter Auto Run If...

Страница 54: ...ass editing this parameter and move to the next parameter you can press the Prev or Next soft key 4 4 Using Memories and Steps PROGRAM Mode only 4 4 1 Selecting a Memory When in the Set screen use the...

Страница 55: ...o cancel the data entry select the Esc soft key 2 Press the List soft key to bring up a list of all programmed memories of the instrument In order to get to the List soft key you will have to press th...

Страница 56: ...y screen Now press the Name soft key This will bring you to the character map for entering the memory name The numeric keypad is also available for creating a memory name Press the top soft key to use...

Страница 57: ...made within the Test Parameter screen will be associated with the individual memory and step location indicated on the display These parameter settings when edited are not universal for each memory an...

Страница 58: ...ent Mode is set to ON test parameters 9 through 28 will no longer be displayed Transient is only selectable when the source is configured for AC output 9 Ramp Up PROGRAM Mode only gives the operator t...

Страница 59: ...attage level is not reached a failure will occur This insures a load is attached to the power source and there is a minimum wattage present 19 Ap Hi Lmt PROGRAM Mode only gives the operator the flexib...

Страница 60: ...27 Q Hi Lmt PROGRAM Mode only gives the operator the flexibility to program a maximum reactive power threshold or floor level When this level is reached a failure will occur Q Hi Lmt is only selectab...

Страница 61: ...phases during 1 3W and 3 4W modes Selecting L1 N will allow the operator to set the limits for the instrument providing L1 N output voltage Selecting L2 N will allow the operator to set the limits for...

Страница 62: ...Trans Volt Trans Site Trans Time and Trans Cycle If the Transient parameter is turned ON you will not see the testing parameters for Ramp Up Timer Unit Delay Dwell Ramp Down Step Cycle A Hi Lmt A Lo...

Страница 63: ...se the soft keys to navigate to the Start Angle or End Angle parameter only selectable for AC output Pressing the Edit soft key will provide one of the following screens Start Angle indicates the star...

Страница 64: ...form at memory 1 step 7 will have a start angle at 90 degrees and the output voltage waveform at memory 2 step 1 will end at a 180 degree angle To change the start angle or end angle use the numeric k...

Страница 65: ...press the Esc soft key When the Enter soft key is pressed and the Memory Cycle is accepted you transition into the next parameter Memory If you wish to bypass editing this parameter and move to the n...

Страница 66: ...the next parameter you can press the Prev or Next soft key 4 6 5 Editing Voltage Use the soft keys to navigate to the Voltage parameter Pressing the Edit soft key will provide the following screen Vol...

Страница 67: ...parameter of frequency output you must press the Next soft key if you do not change the voltage setting If you wish to bypass editing this parameter and move to the next parameter you can press the Pr...

Страница 68: ...save the parameter press the Enter soft key To cancel the editing of the Transient mode press the Esc soft key When the Enter soft key is pressed the Transient mode is accepted and you transition int...

Страница 69: ...is pressed the voltage is accepted and you transition into the next parameter Trans Site If you wish to bypass editing this parameter and move to the next parameter you can press the Prev or Next soft...

Страница 70: ...Pressing the Edit soft key will provide the following screen Trans Time indicates the Transient time that is programmed into the instrument Transient Pulse Width Range indicates the Transient pulse wi...

Страница 71: ...programmed into the instrument If the Transient Trig mode is ON the transient parameters previously programmed will trigger automatically once the test starts This will continue to be active until the...

Страница 72: ...nd move to the next parameter you can press the Prev or Next soft key Parameter is only available if the Transient parameter is turned ON 4 6 12 Editing Ramp Up PROGRAM Mode only Use the soft keys to...

Страница 73: ...avigate to the Timer Unit parameter Pressing the Edit soft key will provide the following screen Timer Unit indicates the timer unit mode that is programmed into the instrument Timer Unit Mode indicat...

Страница 74: ...epted and you transition into the next parameter Dwell If you wish to bypass editing this parameter and move to the next parameter you can press the Prev or Next soft key 4 6 15 Editing Dwell PROGRAM...

Страница 75: ...own time range that can be programmed into the instrument To change the ramp down time use the numeric keypad and type the time Once you type in a number a shaded black box will begin blinking acknowl...

Страница 76: ...cycle is accepted and you transition into the next parameter A Hi Lmt If you wish to bypass editing this parameter and move to the next parameter you can press the Prev or Next soft key 4 6 18 Editing...

Страница 77: ...the Esc soft key to move back to the Current Parameter screen When the Enter soft key is pressed the current is accepted and you transition into the next parameter P Hi Lmt If you wish to bypass editi...

Страница 78: ...er soft key is pressed the power is accepted and you transition into the next parameter Ap Hi Lmt If you wish to bypass editing this parameter and move to the next parameter you can press the Prev or...

Страница 79: ...screen When the Enter soft key is pressed the peak current is accepted and you transition into the next parameter CF Hi Lmt If you wish to bypass editing this parameter and move to the next parameter...

Страница 80: ...or Parameter screen When the Enter soft key is pressed the crest factor is accepted and you transition into the next parameter PF Hi Lmt If you wish to bypass editing this parameter and move to the ne...

Страница 81: ...r or press the Esc key to move back to the Power Factor Parameter screen When the Enter soft key is pressed the power factor is accepted and you transition into the next parameter VA Hi Lmt If you wis...

Страница 82: ...is being changed Press the Enter soft key to accept the parameter or press the Esc key to move back to the Apparent Power Parameter screen When the Enter soft key is pressed the apparent power is acce...

Страница 83: ...ging the parameter is being changed Press the Enter soft key to accept the parameter or press the Esc key to move back to the Reactive Power Parameter screen When the Enter soft key is pressed the pea...

Страница 84: ...key is pressed the prompt is accepted and you transition into the next parameter Step Cycle If you wish to bypass editing this parameter and move to the next parameter you can press the Prev or Next s...

Страница 85: ...ting mode for operating two instruments in a master slave configuration Phase Setting Mode indicates the Phase Setting mode that can be programmed into the instrument The Phase Setting Modes available...

Страница 86: ...lts soft key The screen will look as follows when you are in the correct screen Press the Result soft key to view the results The screen will look as follows If you have multiple steps linked together...

Страница 87: ...outine according to the parameters currently programmed into the instrument when the Test Reset key is pressed However there is no test time associated with the MANUAL Mode The output is continuous un...

Страница 88: ...will be flashing waiting for a voltage value to be entered from the numeric keypad Once the value has been typed into the instrument you must press the Enter soft key to accept the value The Esc soft...

Страница 89: ...charge time The Test Reset LED flashes during this ramp down period to indicate the output is still active If you press the Meter soft key a shaded black box will highlight the meter parameters P or A...

Страница 90: ...meter parameters of F A P Q CF Ap VA PF and the display will read the output on the on the right side of the display Every time the meter key is pressed it will toggle through the meter parameters If...

Страница 91: ...y Knob is disabled If you press the Trig soft key you will hear a beep which is notification that the trigger has been activated for the Transient parameters that have been entered into the instrument...

Страница 92: ...has been typed into the instrument you must press the Enter soft key to accept the value The Esc soft key is available to exit out of this mode and move back to the test screen The Rotary Knob on the...

Страница 93: ...up to 600 VAC by configuring the two sources to output voltage at 180 degrees apart If three 3 instruments are interconnected 3 4W mode is available This mode allows the operator to configure the ins...

Страница 94: ...following diagrams detail the correct setup for configuring multiple 300XAC power sources to operate in Parallel and Polyphase modes Make sure that the instruments are OFF before attempting to make a...

Страница 95: ...wiring diagram Polyphase Mode 3 4W In this configuration the operator must connect the Neutrals of all sources together and utilize the Line outputs to achieve full voltage See the figure below for th...

Страница 96: ...propriate output connections and verifying the interface cable s are connected correctly turn on the power to all instruments The initialization screen will be displayed If a slave instrument fails to...

Страница 97: ...e No soft key to disable the second slave instrument After the Yes or No soft key has been pressed the set screen will be displayed The set screen will change depending on the type of mode for which t...

Страница 98: ...rs have been entered into the instrument the operator may begin the test While a test is running the front panel display will include the Phase key Pressing the Phase key allows the operator to view t...

Страница 99: ...99 If the power to a slave instrument is turned off during operation or the interface cable is unplugged the master instrument display will show the following message...

Страница 100: ...Output Voltage Protection A SH Amplifier Shutdown Protection 7 1 OTP Over Temperature Protection Displayed if the heat sink of the instrument has exceeded 130 C The voltage and current displays will s...

Страница 101: ...occurs on the next power up cycle on the displays will show Volt Err 7 5 A SH Amplifier Shutdown Protection Displayed if the amplifier is in an abnormal condition The LED indicator for the Test Reset...

Страница 102: ...ROCESSING Connection between PIN 5 PIN 6 Closes when test initialized and opens after test is completed 8 2 Signal Input 7 Memory Recall Opt 04 The 300XAC Series also provides an optional remote input...

Страница 103: ...nnection between PIN 2 PIN 5 Momentary contact closure Memory Input Control Selection of up to 7 memory locations is achieved by using a Normally Open N O Momentary Button The truth table below provid...

Страница 104: ...RS 232 Interface This interface is standard on the 300XAC series This interface provides all of the control commands and parameter setting commands of the GPIB interface with the exception of the 488...

Страница 105: ...nput buffer will accumulate the data being sent from the instrument including the ACK and NAK response strings until the controller has read it When the strings or command has been sent it must be ter...

Страница 106: ...receive process and send messages over the bus The interface functions are listed in the chart below GPIB 488 1 INTERFACE FUNCTIONS Interface Function Subset Description Source Handshake SH1 Complete...

Страница 107: ...E 488 read command to retrieve the data from the device s output buffer 9 4 1 Basic Commands and Query Commands The following commands are used to control actual output voltage and current from the in...

Страница 108: ...ue and timer metering The syntax for the command response is memory step status frequency voltage current power peak current power factor timer Each meter will contain only the value and not the units...

Страница 109: ...le a test is in process TDVA Read the active apparent power value being displayed while a test is in process TDTIMER Read the active timer meter value being displayed while a test is in process METER...

Страница 110: ...ults A meter data RDB XX Results B meter data RDC XX Results C meter data RDE XX Results meter data Memory Step Status Freq Volt Curr Power APeak PF Q CF VA Timer Memory Status Freq Volt Curr Power AP...

Страница 111: ...ng L1 N meter data TDL2N Testing L1 N meter data TDL1L2 Testing L1 L2 meter data RDL1N XX Results L1 N meter data RDL2N XX Results L2 N meter data RDL1L2 XX Results L1 L2 meter data Memory Step Status...

Страница 112: ...XX 0 359 EAG END ANGLE 0 359 MC XXXX MEMORY CYCLE XXXX XXXX 0 9999 0 Continue 1 OFF XXXX 0 9999 0 Continue 1 OFF MC MEMORY CYCLE 0 9999 0 9999 MEMORY X MEMORY X X 1 50 MEMORY MEMORY 1 50 STEP X STEP X...

Страница 113: ...2 0 R 1 S 2 T 1 3W X 0 1 0 L1 N 1 L2 N PS PHASE SET 3 4W 0 2 1 3W 0 1 AHI XXXX A HI XXXX A AHI A HI See Note1 See Note2 A ALO XXXX A LO XXXX A ALO A LO See Note1 See Note2 A PHI XXXX POWER HI XXX X W...

Страница 114: ...o modify the system parameters for the instrument These commands require a parameter value to be included with the command The companion query command will read the parameter using the same value that...

Страница 115: ...4W 2 Parallel 3 1 3W SSI X SYNC SIGNAL X X 0 3 0 OFF 1 START 2 EVENT 3 FREQ X 0 2 0 OFF 1 START 2 EVENT SSI SYNC SIGNAL 0 3 0 2 9 4 6 IEEE 488 2 Common Commands These commands are required by the IEEE...

Страница 116: ...116 1 Test Complete OK WAI Wait for next command...

Страница 117: ...T BIT 3 08H 8 Process BIT 4 10H 16 Message Available BIT 5 20H 32 Standard Event ESB BIT 6 40H 64 Request Service MSS BIT 7 80H 128 Prompt SRE value Service Request Enable value 0 255 SRE Service Requ...

Страница 118: ...le register controls which bits will be logically ORed together to generate the Event Summary bit 5 ESB within the Status Byte ESE Queries the Standard Event enable register Returns the decimal value...

Страница 119: ...119 masks from non volatile memory at power ON PSC Queries the power on status clear setting Returns 0 or 1...

Страница 120: ...measuring millivolts DC and 115VAC 400VDC Oscilloscope Required Measurement Equipment 475k watt resistor 11 1125Watt minimum resistor 310XAC 5 5 2250Watt minimum resistor 320XAC 2 75 4500Watt minimum...

Страница 121: ...f the instrument to the Oscilloscope 2 Adjust the Oscilloscope to approximately 200mV 10us This will allow viewing of the high frequency noise 3 Set the output voltage to 0 volts in the low voltage ra...

Страница 122: ...designed the JP1 on the ANG66000 board to disable this hardware circuit function now Note2 We will adjust the DC Offset voltage before leaving our factory The DC Offset value is stable for a long time...

Страница 123: ...ue is displayed on the current meter Model Value 310XAC 9 85 amps 320XAC 19 70 amps 340XAC 39 40 amps 360XAC 59 10 amps 5 Wait 15 seconds 6 Rotate VR1 of the CON61000 board counter levorotary until th...

Страница 124: ...age 150 0V Voltage 300 0 V Current xx xxA Power xxxxW and A Peak xx xA The actual values for the Current Power and A Peak will change according to the model number For example if you are calibrating t...

Страница 125: ...r down arrow soft keys to navigate to the Voltage 300 0V parameter and press the Select soft key Follow the prompt message provided on the display and press the Test Reset button to move into the cali...

Страница 126: ...mode screen Enter the current reading from the ammeter with the numeric keypad When the value has been selected press the Enter soft key and you will be moved to the next calibration parameter The so...

Страница 127: ...rameter The soft keys Volt and Volt are available if needed to adjust the voltage output of the instrument to set a proper wattage value if a non recommended load is used If you press the Esc soft key...

Страница 128: ...t key and you will be moved to the next calibration parameter Volt 150 0V The soft keys Volt and Volt are available if needed to adjust the voltage output of the instrument to set a proper peak curren...

Страница 129: ...ne of electrical safety testers to automatically recall memory locations within the AC power source This option replaces the standard USB RS 232 interface 11 4 Opt 06 Ethernet Card The Ethernet Card o...

Страница 130: ...GPIB control Default Settings The default settings for the Ethernet interface are as follows IP Setup AUTO IP Address 010 000 000 000 Gateway IP 000 000 000 000 Subnet Mask 255 000 000 000 The source...

Страница 131: ...To be completed by Network Administrator Ethernet Card Address ______ ______ ______ ______ ______ Device Name _____________________ Device IP Address _______ _______ _______ _______ Gateway IP Addres...

Страница 132: ...sh a connection with the server anytime the user modifies a parameter and exits the Ethernet Card Parameters Menu or uses the command set at the end of this option description Thus if the IP Setup is...

Страница 133: ...XAC to request an IP address automatically from the network to which it is connected The Ethernet Card will wait for an IP Address for approximately 20 seconds If the APT 300XAC successfully receives...

Страница 134: ...server to which it is connected When AUTO is selected the APT 300XAC will attempt to automatically request an IP Address from the server upon power up To resolve the IP Address automatically the APT 3...

Страница 135: ...hlight the Gateway IP parameter using the soft keys When the Gateway IP parameter is highlighted press the Edit soft key A specific Gateway IP must be entered into this field if the IP Setup parameter...

Страница 136: ...hted press the Edit soft key The Device Name screen will appear as follows From this screen you may enter a Device Name for the APT 300XAC The Device Name is used to identify the APT 300XAC on your se...

Страница 137: ...djustable 11 4 11 Barcode Input Highlight the Barcode INPUT parameter using the soft keys When the Barcode INPUT parameter is highlighted press the Edit soft key The Barcode INPUT parameter can be set...

Страница 138: ...characters However if the user names a test file with the maximum 10 characters this function will still initiate a test when a product s barcode begins with those first 10 characters even if the barc...

Страница 139: ...atching file name The test file name is limited to 10 characters However if the user names a test file with the maximum 10 characters this function will still load a test file if the first 10 characte...

Страница 140: ...espond with the 06 hex 6 decimal Acknowledge ACK ASCII control code if the transfer was recognized by the instrument If there was an error with the command string the instrument will respond with 15 h...

Страница 141: ...1 8 seconds Wait times are approximate and can vary based on the user s network 11 5 Opt 08 Linking Card This option enables the instrument to interconnect to up to two 2 other 300XAC instruments for...

Страница 142: ...This is to protect the user in terms of safety and to insure a high accuracy of operation and measurement of this instrument at all times User Modification Modification by the user of the instrument...

Страница 143: ...on 360XAC 39179 1 Shorting Bar for Input Parallel connection 360XAC Panel Components 37793 1 Panel Bezel Plastic 3U 38109 1 SW1 Power Switch 2P 10A 250V 38977 1 EVR1 Rotary Encoder 38973 1 Rotary Knob...

Страница 144: ...rect Board 320XAC 39127 1 PFC61000 PF Correct Board 340XAC 39128 3 PFC61000 PF Correct Board 360XAC 39129 1 FLY61000 FLY Back Board 310XAC 320XAC 39130 1 FLY61000 FLY Back Board 340XAC 360XAC 39131 1...

Страница 145: ...F2 Fuse 20A Slow 30mm for PFC61000 340XAC 39185 1 PFC61000 2 DDC61000 F2 Fuse Holder 30A 30mm for DDC61000 and PFC61000 39187 1 310XAC 3 360XAC F1 Fuse 15A Fast 38mm for PFC61000 310XAC 360XAC 39188 1...

Страница 146: ...146 14 Schematics Index Unless specified in the Model column of this table schematics are valid for all models...

Отзывы: