ALTENERGY POWER SYSTEM INC.
12
Version
:
4.1
The numbers above mean that there are 15 sets of micro-inverters that should
have been connected to the ECU while in fact, there are only 12 sets of
micro-inverters to be connected.
Enter the ECU menu. Hold the Menu button until the LCD displays: “Shutdown.”
Release the Menu button, and the following items will appear:
Choose “Ok”, and the system of inverter will shut down. Choose “Cancel”, ECU
will exit the menu. If within one minute without pressing the button again, then
automatically exit the menu button.
4.3 Restore the factory set operation
The following diagram guides to the connectors back of APS-ECU.
RESET
For the ECU restoring the factory set, simply press the “Reset” button for three
seconds or longer, ECU will automaticly return to the factory default settings.
4.4 Troubleshooting
Potential Problems and Solutions
IP Address Problem:
If the IP address displayed on the ECU’s LCD does not
match the subnet on your internal network and shows “60.190.131.190”, it
means that it was unsuccessful in obtaining a DHCP IP address from your router.
·
Check network connectivity to the router or other DHCP server. You may
Connected: 12
Total: 15
Ok
Cancel